- Linearity Error:
- AI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AO1, AO2 +/- 0.2 % analog output
- Circularity Profile:
- ENVEOLI2007011EN
- Switching Frequency:
- 2...12 kHz adjustable || 4...12 kHz with derating factor
- Maximum Switching Current:
- relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC || relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2
- Type Of Polarization:
- no impedance
- Maximum Thdi:
- <48 % from 80...100 % of load IEC 61000-3-12
- Line Current:
- 33.4 A 380 V normal duty) || 28.9 A 480 V normal duty) || 27.7 A 380 V heavy duty) || 24.4 A 480 V heavy duty)
- Option Card:
- slot A communication module, Profibus DP V1 || slot A communication module, PROFINET || slot A communication module, DeviceNet || slot A communication module, Modbus TCP/EtherNet/IP || slot A communication module, CANopen daisy chain RJ45 || slot A c
- Motor Slip Compensation:
- automatic whatever the load || adjustable || not available in permanent magnet motor law || can be suppressed
- Safety Function:
- STO (safe torque off) SIL 3
- Mercury Free:
- Yes
- Sampling Duration:
- 2 ms +/- 0.5 ms DI1...DI4) - discrete input || 5 ms +/- 1 ms DI5, DI6) - discrete input || 5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input || 10 ms +/- 1 ms AO1) - analog output
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Minimum Switching Current:
- relay output R1, R2, R3 5 mA 24 V DC
- Permissible Temporary Current Boost:
- 1.1 x In 60 s normal duty) || 1.5 x In 60 s heavy duty)
- Transmission Rate:
- 10, 100 Mbits || 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
- Discrete Input Type:
- DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V)
- Nominal Switching Frequency:
- 4 kHz
- Noise Level:
- 59.5 dB
- Product Specific Application:
- process and utilities
- Discrete Input Logic:
- 16 preset speeds
- Enclosure Mounting:
- with heat sink
- Variant:
- standard version
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Apparent Power:
- 24 kVA 480 V normal duty) || 20.3 kVA 480 V heavy duty)
- Power Range:
- 15-25 kW 380-440 V 3 phase || 15-25 kW 480-500 V 3 phase
- Ambient Air Temperature For Operation:
- -15-50 °C without derating) || 50-60 °C with derating factor)
- Noise Level:
- 59.5 dB 86/188/EEC
- Pollution Degree:
- 2
- Output Voltage:
- <= power supply voltage
- Product Or Component Type:
- variable speed drive
- Connector Type:
- RJ45 on the remote graphic terminal)Ethernet/Modbus TCP || RJ45 on the remote graphic terminal)Modbus serial
- Synchronous Motor Control Profile:
- permanent magnet motor || synchronous reluctance motor
- Analogue Output Number:
- 2
- Electromagnetic Compatibility:
- electrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge im
- Refresh Time:
- relay output R1, R2, R3)5 ms +/- 0.5 ms)
- Relay Output Type:
- configurable relay logic R1 fault relay NO/NC 100000 cycles || configurable relay logic R2 sequence relay NO 100000 cycles || configurable relay logic R3 sequence relay NO 100000 cycles
- Motor Power Kw:
- 18.5 kW normal duty) || 15 kW heavy duty)
- Overvoltage Category:
- III
- Relative Humidity:
- 5-95 % without condensation IEC 60068-2-3
- Rohs Exemption Information:
- Yes
- Relay Output Number:
- 3
- Marking:
- CE
- Discrete Input Number:
- 8
- Vibration Resistance:
- 1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6 || 1 gn 13-200 Hz)IEC 60068-2-6
- Discrete Output Number:
- 0
- China Rohs Regulation:
- X
- Device Short Name:
- ATV630
- Supply Frequency:
- 50...60 Hz - 5...5 %
- Maximum Transient Current:
- 43.1 A 60 s normal duty) || 47.6 A 60 s heavy duty)
- Analogue Input Type:
- AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits || AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits
- Exchange Mode:
- half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
- Width:
- 195 mm
- Upgradeability:
- Upgraded components available
- Continuous Output Current:
- 39.2 A 4 kHz normal duty || 31.7 A 4 kHz heavy duty
- Assembly Style:
- with heat sink
- Prospective Line Isc:
- 50 kA
- Maximum Output Frequency:
- 500 kHz
- Environmental Disclosure:
- ENVPEP2007011EN
- Analogue Input Number:
- 3
- Speed Drive Output Frequency:
- 0.1-500 Hz
- Power Dissipation In W:
- natural convection 67 W 380 V 4 kHz || forced convection 460 W 380 V 4 kHz
- Input Compatibility:
- DI1...DI6 discrete input level 1 PLC IEC 61131-2 || DI5, DI6 discrete input level 1 PLC IEC 65A-68 || STOA, STOB discrete input level 1 PLC IEC 61131-2
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)
- Physical Interface:
- Ethernet || 2-wire RS 485
- Communication Port Protocol:
- Modbus TCP || Modbus serial || Ethernet
- Sustainable Offer Status:
- Green Premium product
- Standards:
- UL 508C || IEC 61800-3 || IEC 61800-3 environment 1 category C2 || EN/IEC 61800-3 environment 2 category C3 || IEC 61800-5-1 || IEC 61000-3-12 || IEC 60721-3 || IEC 61508 || IEC 13849-1
- Method Of Access:
- slave Modbus TCP
- Pollution Degree:
- 2 IEC 61800-5-1
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Braking To Standstill:
- by DC injection
- Volume Of Cooling Air:
- 215 m3/h
- [Us] Rated Supply Voltage:
- 380...480 V
- Ip Degree Of Protection:
- IP20IEC 61800-5-1 || IP20IEC 60529
- Accuracy:
- +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input || +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
- Analogue Output Type:
- software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 10 bits || software-configurable current DQ-, DQ+ 30 V DC || software-configurable current DQ-, DQ+ 100 mA
- Mounting Mode:
- cabinet mount
- Type Of Cooling:
- forced convection
- Electrical Connection:
- control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 || line side screw terminal 10...16 mm² AWG 8...AWG 6 || motor screw terminal 10...16 mm² AWG 8...AWG 6
- Number Of Addresses:
- 1-247 Modbus serial
- Acceleration And Deceleration Ramps:
- linear adjustable separately from 0.01...9999 s
- Quantity Per Set:
- 1
- Ambient Air Temperature For Storage:
- -40-70 °C
- Product Certifications:
- CSA || ATEX zone 2/22 || ATEX INERIS || DNV-GL || UL || TÃV
- Product Destination:
- asynchronous motors || synchronous motors
- Depth:
- 225.5 mm
- Frequency Resolution:
- display unit 0.1 Hz || analog input 0.012/50 Hz
- Isolation:
- between power and control terminals
- Protection Type:
- thermal protection motor || safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-c
- Supply:
- external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection || internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for d
- Height:
- 480 mm
- Data Format:
- 8 bits, configurable odd, even or no parity
- Regulation Loop:
- adjustable PID regulator
- [Us] Rated Supply Voltage:
- 380...480 V - 15...10 %
- Shock Resistance:
- 15 gn 11 ms IEC 60068-2-27
- Insulation Resistance:
- > 1 MOhm 500 V DC for 1 minute to earth
- Asynchronous Motor Control Profile:
- optimized torque mode || variable torque standard || constant torque standard
- Maximum Horse Power Rating:
- 25 hp normal duty || 20 hp heavy duty
- Emc Filter:
- integrated 10 m IEC 61800-3 category C2 || integrated 50 m IEC 61800-3 category C3 || with EMC plate option
- Phase:
- 3 phase
- Operating Position:
- vertical +/- 10 degree
- Operating Altitude:
- <= 3280.84 ft (1000 m) without derating || 1000...4800 m with current derating 1 % per 100 m
- Range Of Product:
- Altivar Process ATV600
- Discrete Input Logic:
- positive logic (source) DI1...DI8), < 5 V, > 11 V || negative logic (sink) DI1...DI8), > 16 V, < 10 V
- Transmission Frame:
- RTU
- Discrete And Process Manufacturing:
- building - HVAC compressor centrifugal || food and beverage processing other application || mining mineral and metal fan || mining mineral and metal pump || oil and gas fan || water and waste water other application || building - HVAC screw compresso
- Local Signalling:
- for local diagnostic 3 LEDs || for embedded communication status 3 LEDs (dual colour) || for communication module status 4 LEDs (dual colour) || for presence of voltage 1 LED (red)
- Net Weight:
- 13.6 kg
- Discrete Output Type:
- relay outputs R1A, R1B, R1C 250 V AC 3000 mA || relay outputs R1A, R1B, R1C 30 V DC 3000 mA || relay outputs R2A, R2C 250 V AC 5000 mA || relay outputs R2A, R2C 30 V DC 5000 mA || relay outputs R3A, R3C 250 V AC 5000 mA || relay outputs R3A, R3C 30 V