Schneider Electric ATV630D55M3 Variable Speed Drive Ip21 55Kw 200V/240V

(No reviews yet) Write a Review
SKU:
ATV630D55M3
UPC:
3.60648E+12
Condition:
New
Pollution Degree:
2 IEC 61800-5-1
Discrete Input Logic:
16 preset speeds
China Rohs Regulation:
X
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Range Of Product:
Altivar Process ATV600
Safety Function:
STO (safe torque off) SIL 3
Discrete Input Type:
DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V)
Product Destination:
asynchronous motors || synchronous motors
Isolation:
between power and control terminals
Product Specific Application:
process and utilities
Speed Drive Output Frequency:
0.1-500 Hz
Pollution Degree:
2
Discrete Output Number:
0
Product Certifications:
UL || ATEX INERIS || TÜV || DNV-GL || CSA || ATEX zone 2/22
Maximum Thdi:
<48 % full load IEC 61000-3-12
Apparent Power:
61.1 kVA 240 V normal duty) || 50 kVA 240 V heavy duty)
Analogue Input Number:
3
Minimum Switching Current:
relay output R1, R2, R3 5 mA 24 V DC
Continuous Output Current:
211 A 2.5 kHz normal duty || 176 A 2.5 kHz heavy duty
Asynchronous Motor Control Profile:
variable torque standard || optimized torque mode || constant torque standard
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Analogue Input Type:
AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits || AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits
Maximum Horse Power Rating:
75 hp normal duty || 60 hp heavy duty
Operating Position:
vertical +/- 10 degree
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Maximum Switching Current:
relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC || relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2
Mounting Mode:
wall mount
Communication Port Protocol:
Modbus TCP || Ethernet || Modbus serial
Overvoltage Category:
III
Nominal Switching Frequency:
2.5 kHz
Circularity Profile:
ENVEOLI1501011EN
Transmission Frame:
RTU
Accuracy:
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input || +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
Standards:
UL 508C || IEC 61800-3 || IEC 61800-3 environment 1 category C2 || EN/IEC 61800-3 environment 2 category C3 || IEC 61800-5-1 || IEC 61000-3-12 || IEC 60721-3 || IEC 61508 || IEC 13849-1
Product Or Component Type:
variable speed drive
Regulation Loop:
adjustable PID regulator
Discrete Input Logic:
positive logic (source) DI1...DI8), < 5 V, > 11 V || negative logic (sink) DI1...DI8), > 16 V, < 10 V
Prospective Line Isc:
50 kA
Depth:
390 mm
Relay Output Type:
configurable relay logic R1 fault relay NO/NC 100000 cycles || configurable relay logic R2 sequence relay NO 100000 cycles || configurable relay logic R3 sequence relay NO 100000 cycles
Analogue Output Type:
software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 10 bits || software-configurable current DQ-, DQ+ 30 V DC || software-configurable current DQ-, DQ+ 100 mA
Marking:
CE
Transmission Rate:
10, 100 Mbits || 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
Quantity Per Set:
1
Operating Altitude:
<= 3280.84 ft (1000 m) without derating || 1000...4800 m with current derating 1 % per 100 m
Sustainable Offer Status:
Green Premium product
Power Range:
55-100 kW 200-240 V 3 phase
Emc Filter:
without EMC filter
Refresh Time:
relay output R1, R2, R3)5 ms +/- 0.5 ms)
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Number Of Addresses:
1-247 Modbus serial
Linearity Error:
AI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AO1, AO2 +/- 0.2 % analog output
Method Of Access:
slave Modbus TCP
Vibration Resistance:
1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6 || 1 gn 13-200 Hz)IEC 60068-2-6
Insulation Resistance:
> 1 MOhm 500 V DC for 1 minute to earth
Line Current:
189 A 200 V normal duty) || 161 A 240 V normal duty) || 156 A 200 V heavy duty) || 134 A 240 V heavy duty)
Shock Resistance:
15 gn 11 ms IEC 60068-2-27
Data Format:
8 bits, configurable odd, even or no parity
Ip Degree Of Protection:
IP00IEC 61800-5-1 || IP00IEC 60529 || IP21 with kit VW3A9704)IEC 61800-5-1 || IP21 with kit VW3A9704)IEC 60529
Type Of Cooling:
forced convection
Motor Slip Compensation:
not available in permanent magnet motor law || automatic whatever the load || adjustable || can be suppressed
Net Weight:
84 kg
Acceleration And Deceleration Ramps:
linear adjustable separately from 0.01...9999 s
Option Card:
slot A communication module, Profibus DP V1 || slot A communication module, PROFINET || slot A communication module, DeviceNet || slot A communication module, Modbus TCP/EtherNet/IP || slot A communication module, CANopen daisy chain RJ45 || slot A c
Maximum Transient Current:
232.1 A 60 s normal duty) || 264 A 60 s heavy duty)
Ambient Air Temperature For Storage:
-40-70 °C
Synchronous Motor Control Profile:
permanent magnet motor || synchronous reluctance motor
Frequency Resolution:
display unit 0.1 Hz || analog input 0.012/50 Hz
Enclosure Mounting:
wall mounted
Rohs Exemption Information:
Yes
Motor Power Kw:
55 kW normal duty) || 45 kW heavy duty)
Volume Of Cooling Air:
600 m3/h
Maximum Output Frequency:
500 kHz
Input Compatibility:
DI1...DI6 discrete input level 1 PLC IEC 61131-2 || DI5, DI6 discrete input level 1 PLC IEC 65A-68 || STOA, STOB discrete input level 1 PLC IEC 61131-2
Braking To Standstill:
by DC injection
Exchange Mode:
half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Analogue Output Number:
2
[Us] Rated Supply Voltage:
200...240 V - 15...10 %
Type Of Polarization:
no impedance
Electrical Connection:
control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 || line side screw terminal 2 x 70...3 x 120 mm² 2 x AWG 2/0...2 x 300 kcmil || motor screw terminal 2 x 70...3 x 120 mm² 2 x AWG 2/0...2 x 300 kcmil
Device Short Name:
ATV630
Connector Type:
RJ45 on the remote graphic terminal)Ethernet/Modbus TCP || RJ45 on the remote graphic terminal)Modbus serial
Relative Humidity:
5-95 % without condensation IEC 60068-2-3
Supply Frequency:
50...60 Hz - 5...5 %
Width:
320 mm
Discrete Input Number:
8
Switching Frequency:
2.5...8 kHz with derating factor || 2...8 kHz adjustable
Supply:
external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection || internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for d
Physical Interface:
Ethernet || 2-wire RS 485
Height:
852 mm
Output Voltage:
<= power supply voltage
Environmental Disclosure:
ENVPEP1501011EN
Protection Type:
thermal protection motor || safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-c
Upgradeability:
Upgraded components available
Electromagnetic Compatibility:
electrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge im
Variant:
standard version
Mercury Free:
Yes
Sampling Duration:
2 ms +/- 0.5 ms DI1...DI4) - discrete input || 5 ms +/- 1 ms DI5, DI6) - discrete input || 5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input || 10 ms +/- 1 ms AO1) - analog output
Ambient Air Temperature For Operation:
-15-50 °C without derating) || 50-60 °C with derating factor)
Local Signalling:
for local diagnostic 3 LEDs || for embedded communication status 3 LEDs (dual colour) || for communication module status 4 LEDs (dual colour) || for presence of voltage 1 LED (red)
Noise Level:
69.9 dB 86/188/EEC
Permissible Temporary Current Boost:
1.1 x In 60 s normal duty) || 1.5 x In 60 s heavy duty)
Discrete Output Type:
relay outputs R1A, R1B, R1C 250 V AC 3000 mA || relay outputs R1A, R1B, R1C 30 V DC 3000 mA || relay outputs R2A, R2C 250 V AC 5000 mA || relay outputs R2A, R2C 30 V DC 5000 mA || relay outputs R3A, R3C 250 V AC 5000 mA || relay outputs R3A, R3C 30 V
[Us] Rated Supply Voltage:
200...240 V
Relay Output Number:
3
Noise Level:
69.9 dB
Phase:
3 phase
Discrete And Process Manufacturing:
building - HVAC compressor centrifugal || food and beverage processing other application || mining mineral and metal fan || mining mineral and metal pump || oil and gas fan || water and waste water other application || building - HVAC screw compresso
Brochure:
View
Catalog:
View
Datasheet:
View
  • Schneider Electric ATV630D55M3 Variable Speed Drive Ip21 55Kw 200V/240V
  • Schneider Electric ATV630D55M3 Variable Speed Drive Ip21 55Kw 200V/240V
  • Schneider Electric ATV630D55M3 Variable Speed Drive Ip21 55Kw 200V/240V
$13,083.74

Description

This Altivar Process ATV600 variable speed drive can feed 3-phase synchronous and asynchronous power motors. It features 3 built-in RJ45 communication ports as standard, 1 Ethernet port, 2 serial ports. It works at a rated supply voltage from 200V to 240V AC. This drive provides up to 30% energy saving when on standby due to the innovative ‘‘Stop and Go’’operation without additional costs. It is suitable for motors with power rating up to 55kW / 75hp for applications requiring slight overload (up to 120%). It is suitable for motors with power rating up to 45kW / 60hp for applications requiring significant overload (up to 150%). It weighs 84kg and its dimensions are, 320mm wide, 852mm high, 390mm deep. This drive is focused on fluids management processing and energy saving, it offers extensive flexibility in water and wastewater, mining, minerals and metals, oil and gas and food and beverage applications. Accessories (fan kit, graphic display terminal) and options (I/O expansion modules, communication modules, EMC input filters) are available with Altivar Process ATV600 drives, depending on the drive rating. It is designed to be mounted in vertical position (+/- 10 °) on a wall. This new concept of drives meets the major needs of process and utilities in terms of equipment efficiency and total cost of ownership by supporting the energy management, asset management and also the overall performance of the process.
View AllClose