Schneider Electric ATV650U40N4U Atv650 Ip55 Ul Type12 4Kw 5Hp 400V/480V
SKU:
ATV650U40N4U
UPC:
3606480907050
MPN:
Condition:
New
Pollution Degree:
3
Motor Slip Compensation:
not available in permanent magnet motor law || automatic whatever the load || adjustable
Refresh Time:
relay output R1, R2, R3)5 ms +/- 0.5 ms)
Maximum Horse Power Rating:
4 hp heavy duty || 5 hp normal duty
China Rohs Regulation:
X
Mounting Mode:
wall mount
Degree Of Protection:
UL type 12 UL 508C
Net Weight:
10.6 kg
Local Signalling:
for embedded communication status 3 LEDs (dual colour) || for communication module status 4 LEDs (dual colour) || for presence of voltage 1 LED (red) || for local diagnostic 3 LEDs
DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V)
Analogue Output Number:
2
Product Destination:
asynchronous motors || synchronous motors
Line Current:
6.7 A 480 V normal duty) || 6 A 380 V heavy duty) || 5.4 A 480 V heavy duty) || 7.6 A 380 V normal duty)
Noise Level:
52 dB
Vibration Resistance:
1 gn 13-200 Hz)IEC 60068-2-6 || 1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6
Overvoltage Category:
III
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Pollution Degree:
2 IEC 61800-5-1
Safety Function:
STO (safe torque off) SIL 3
Electromagnetic Compatibility:
radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5 || conducted radio-frequency
Minimum Switching Current:
relay output R1, R2, R3 5 mA 24 V DC
Ambient Air Temperature For Storage:
-40-70 °C
Regulation Loop:
adjustable PID regulator
Data Format:
8 bits, configurable odd, even or no parity
Method Of Access:
slave Modbus TCP
Discrete Input Number:
8
Range Of Product:
Altivar Process ATV600
Discrete Output Type:
relay outputs R1A, R1B, R1C 250 V AC 3000 mA || relay outputs R1A, R1B, R1C 30 V DC 3000 mA || relay outputs R2A, R2C 250 V AC 5000 mA || relay outputs R2A, R2C 30 V DC 5000 mA || relay outputs R3A, R3C 250 V AC 5000 mA || relay outputs R3A, R3C 30 V
Protection Type:
safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-circuit protection drive || m
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Relative Humidity:
5-95 % without condensation IEC 60068-2-3
Analogue Output Type:
software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 10 bits || software-configurable current DQ-, DQ+ 30 V DC || software-configurable current DQ-, DQ+ 100 mA
Linearity Error:
AO1, AO2 +/- 0.2 % analog output || AI1, AI2, AI3 +/- 0.15 % of maximum value analog input
Option Card:
slot A communication module, PROFINET || slot A communication module, DeviceNet || slot A communication module, Modbus TCP/EtherNet/IP || slot A communication module, CANopen daisy chain RJ45 || slot A communication module, CANopen SUB-D 9 || slot A
Connector Type:
RJ45 on the remote graphic terminal)Modbus serial || RJ45 on the remote graphic terminal)Ethernet/Modbus TCP
Synchronous Motor Control Profile:
synchronous reluctance motor || permanent magnet motor
Supply Frequency:
50...60 Hz - 5...5 %
Product Specific Application:
process and utilities
Number Of Addresses:
1-247 Modbus serial
Type Of Polarization:
no impedance
Sustainable Offer Status:
Green Premium product
Permissible Temporary Current Boost:
1.5 x In 60 s heavy duty) || 1.1 x In 60 s normal duty)
Apparent Power:
4.5 kVA 480 V heavy duty) || 5.6 kVA 480 V normal duty)
constant torque standard || optimized torque mode || variable torque standard
Supply:
internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for digital inputs and STO 24 V DC 21-27 V), <200 mA overload and short-circuit protection || external suppl
Rohs Exemption Information:
Yes
Transmission Frame:
RTU
Maximum Output Frequency:
500 kHz
Sampling Duration:
5 ms +/- 1 ms DI5, DI6) - discrete input || 5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input || 10 ms +/- 1 ms AO1) - analog output || 2 ms +/- 0.5 ms DI1...DI4) - discrete input
[Us] Rated Supply Voltage:
380...480 V - 15...10 %
Product Certifications:
ATEX INERIS || UL || ABS || Bureau Veritas || CSA || DNV-GL
Upgradeability:
Upgraded components available
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Acceleration And Deceleration Ramps:
linear adjustable separately from 0.01...9999 s
Ip Degree Of Protection:
IP55IEC 60529 || IP55IEC 61800-5-1
Analogue Input Number:
3
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Circularity Profile:
ENVEOLI1508009EN
Quantity Per Set:
1
Height:
678 mm
Width:
264 mm
Depth:
272 mm
Phase:
3 phase
Maximum Switching Current:
relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC || relay output R1, R2, R3 resistive, cos phi = 1 3
Frequency Resolution:
analog input 0.012/50 Hz || display unit 0.1 Hz
Analogue Input Type:
AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits || AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits
Variant:
standard version
Emc Filter:
integrated 50 m IEC 61800-3 category C2 || integrated 150 m IEC 61800-3 category C3
This Altivar Process ATV600 variable speed drive can feed 3-phase synchronous and asynchronous power motors. This variable speed drive features an integrated EMC filter with 50m and 150m cable...