The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Device Short Name:
ATV650
Protection Type:
safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-circuit protection drive || m
Transmission Frame:
RTU
Motor Power Kw:
5.5 kW heavy duty) || 7.5 kW normal duty)
Refresh Time:
relay output R1, R2, R3)5 ms +/- 0.5 ms)
Noise Level:
52 dB
Speed Drive Output Frequency:
0.1-500 Hz
Nominal Switching Frequency:
4 kHz
Output Voltage:
<= power supply voltage
Regulation Loop:
adjustable PID regulator
China Rohs Regulation:
X
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for digital inputs and STO 24 V DC 21-27 V), <200 mA overload and short-circuit protection || external suppl
Height:
678 mm
Frequency Resolution:
analog input 0.012/50 Hz || display unit 0.1 Hz
Minimum Switching Current:
relay output R1, R2, R3 5 mA 24 V DC
Sustainable Offer Status:
Green Premium product
Safety Function:
STO (safe torque off) SIL 3
Depth:
299 mm
Product Certifications:
TÃV || UL || CSA || DNV-GL || Bureau Veritas || ABS || ATEX INERIS
Synchronous Motor Control Profile:
synchronous reluctance motor || permanent magnet motor
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Analogue Output Number:
2
Electromagnetic Compatibility:
radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5 || conducted radio-frequency
Maximum Transient Current:
19.1 A 60 s heavy duty) || 18.2 A 60 s normal duty)
Circularity Profile:
ENVEOLI1508009EN
Insulation Resistance:
> 1 MOhm 500 V DC for 1 minute to earth
Sampling Duration:
5 ms +/- 1 ms DI5, DI6) - discrete input || 5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input || 10 ms +/- 1 ms AO1) - analog output || 2 ms +/- 0.5 ms DI1...DI4) - discrete input
Upgradeability:
Upgraded components available
Mercury Free:
Yes
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Motor Slip Compensation:
not available in permanent magnet motor law || automatic whatever the load || can be suppressed || adjustable
Type Of Cooling:
forced convection
Data Format:
8 bits, configurable odd, even or no parity
Analogue Output Type:
software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 10 bits || software-configurable current DQ-, DQ+ 30 V DC || software-configurable current DQ-, DQ+ 100 mA
Asynchronous Motor Control Profile:
constant torque standard || optimized torque mode || variable torque standard
for embedded communication status 3 LEDs (dual colour) || for communication module status 4 LEDs (dual colour) || for presence of voltage 1 LED (red) || for local diagnostic 3 LEDs
Communication Port Protocol:
Ethernet || Modbus serial || Modbus TCP
Discrete Output Number:
0
Linearity Error:
AO1, AO2 +/- 0.2 % analog output || AI1, AI2, AI3 +/- 0.15 % of maximum value analog input
Switching Frequency:
4...12 kHz with derating factor || 2...12 kHz adjustable
Apparent Power:
7.6 kVA 480 V heavy duty) || 9.9 kVA 480 V normal duty)
Analogue Input Type:
AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits || AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits
Discrete Input Number:
8
Discrete Input Logic:
16 preset speeds
Mounting Mode:
wall mount
Maximum Switching Current:
relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC || relay output R1, R2, R3 resistive, cos phi = 1 3
11.9 A 480 V normal duty) || 10.5 A 380 V heavy duty) || 9.2 A 480 V heavy duty) || 13.8 A 380 V normal duty)
Width:
264 mm
Permissible Temporary Current Boost:
1.5 x In 60 s heavy duty) || 1.1 x In 60 s normal duty)
Option Card:
slot A communication module, PROFINET || slot A communication module, DeviceNet || slot A communication module, Modbus TCP/EtherNet/IP || slot A communication module, CANopen daisy chain RJ45 || slot A communication module, CANopen SUB-D 9 || slot A
Ambient Air Temperature For Storage:
-40-70 °C
Accuracy:
+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output || +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
Prospective Line Isc:
50 kA
Operating Altitude:
1000...4800 m with current derating 1 % per 100 m || <= 3280.84 ft (1000 m) without derating
Connector Type:
RJ45 on the remote graphic terminal)Modbus serial || RJ45 on the remote graphic terminal)Ethernet/Modbus TCP
Ip Degree Of Protection:
IP55IEC 60529 || IP55IEC 61800-5-1
Acceleration And Deceleration Ramps:
linear adjustable separately from 0.01...9999 s
Relative Humidity:
5-95 % without condensation IEC 60068-2-3
Pollution Degree:
2 EN/IEC 61800-5-1
Degree Of Protection:
UL type 12 UL 508C
Range Of Product:
Altivar Process ATV600
Discrete Input Type:
DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V)
40-50 °C with derating factor) || -15-40 °C without derating)
Isolation:
between power and control terminals
Relay Output Number:
3
Braking To Standstill:
by DC injection
Type Of Polarization:
no impedance
Shock Resistance:
15 gn 11 ms IEC 60068-2-27
[Us] Rated Supply Voltage:
380...480 V
Pollution Degree:
3
Maximum Horse Power Rating:
7.5 hp heavy duty || 10 hp normal duty
Product Or Component Type:
variable speed drive
Environmental Disclosure:
ENVPEP1508009EN
[Us] Rated Supply Voltage:
380...480 V - 15...10 %
Maximum Thdi:
<48 % from 80...100 % of load IEC 61000-3-12
Rohs Exemption Information:
Yes
Marking:
CE
Physical Interface:
Ethernet || 2-wire RS 485
Product Specific Application:
process and utilities
Supply Frequency:
50...60 Hz - 5...5 %
Electrical Connection:
motor screw terminal 6...10 mm² || line side screw terminal 4...6 mm² || control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 || motor screw terminal 6...10 mm² AWG 10...AWG 8 || line side screw terminal 4...6 mm² AWG 12...AWG10
Emc Filter:
integrated 50 m EN/IEC 61800-3 category C2 || integrated 150 m EN/IEC 61800-3 category C3
Continuous Output Current:
12.7 A 4 kHz heavy duty || 16.5 A 4 kHz normal duty
Method Of Access:
slave Modbus TCP
Operating Position:
vertical +/- 10 degree
Exchange Mode:
half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Vibration Resistance:
1 gn 13-200 Hz)IEC 60068-2-6 || 1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6
Discrete Output Type:
relay outputs R1A, R1B, R1C 250 V AC 3000 mA || relay outputs R1A, R1B, R1C 30 V DC 3000 mA || relay outputs R2A, R2C 250 V AC 5000 mA || relay outputs R2A, R2C 30 V DC 5000 mA || relay outputs R3A, R3C 250 V AC 5000 mA || relay outputs R3A, R3C 30 V
This Altivar Process ATV600 variable speed drive can feed 3-phase synchronous and asynchronous power motors. This variable speed drive features an integrated EMC filter with 50m and 150m cable...