AI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AQ1, AQ2 +/- 0.2 % analog output
Ambient Air Transport Temperature:
-40-70 °C
Variant:
standard version || with braking chopper
Asynchronous Motor Control Profile:
optimized torque mode || variable torque standard || constant torque standard
Product Or Component Type:
variable speed drive
Sampling Duration:
2 ms +/- 0.5 ms DI1...DI8) - discrete input || 5 ms +/- 1 ms DI7, DI8) - pulse input || 1 ms +/- 1 ms AI1, AI2, AI3) - analog input || 5 ms +/- 1 ms AQ1, AQ2) - analog output
1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6 || 1 gn 13-200 Hz)IEC 60068-2-6
Number Of Addresses:
1-247 Modbus serial
Electrical Connection:
control screw terminal 0.5...1.5 mm² AWG 20...AWG 16 || motor screw terminal 6...10 mm² AWG 10...AWG 8 || line side screw terminal 6 mm² AWG 10 || DC bus screw terminal 6 mm² AWG 10
Range Of Product:
Altivar Process ATV900
Quantity Per Set:
1
Method Of Access:
slave Modbus TCP
Network Frequency:
50-60 Hz
Option Card:
slot A communication module Profibus DP V1 || slot A communication module PROFINET || slot A communication module DeviceNet || slot A communication module EtherCAT || slot A communication module CANopen daisy chain RJ45 || slot A communication module
Motor Slip Compensation:
can be suppressed || automatic whatever the load || not available in permanent magnet motor law || adjustable
With Safety Function Safe Torque Off (Sto):
TRUE
Mounting Mode:
wall mount
Assembly Style:
enclosed
Sustainable Offer Status:
Green Premium product
Maximum Acceleration Under Shock Impact (During Operation):
With Safety Function Safe Brake Management (Sbc/Sbt):
TRUE
Power Dissipation In W:
forced convection 152 W 600 V 4 kHz || natural convection 114 W 600 V 4 kHz
Phase:
3 phase
Overvoltage Category:
III
With Safety Function Safe Programmable Logic:
FALSE
Relay Output Number:
3
Maximum Output Voltage:
600.0 V
Maximum Switching Current:
relay output R1 resistive, cos phi = 1 3 A 250 V AC || relay output R1 resistive, cos phi = 1 3 A 30 V DC || relay output R1 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1 inductive, cos phi = 0.4 7 ms 2 A 30 V DC || relay output R2, R
Net Weight:
5.5 kg
Ambient Air Temperature For Operation:
-15-50 °C without derating) || 50-60 °C with derating factor)
Product Specific Application:
process for industrial
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
[Us] Rated Supply Voltage:
600 V - 15...10 %
Brake Chopper Integrated:
TRUE
Operating Altitude:
<= 3280.84 ft (1000 m) without derating || 1000...4800 m with current derating 1 % per 100 m
Braking To Standstill:
by DC injection
Analogue Output Type:
software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 500 Ohm 10 bits
Environmental Characteristic:
chemical pollution resistance class 3C3 IEC 60721-3-3 || dust pollution resistance class 3S3 IEC 60721-3-3
China Rohs Regulation:
X
Mercury Free:
Yes
Environmental Disclosure:
ENVPEP1707007EN
Maximum Transient Current:
21.6 A 60 s normal duty) || 20.3 A 60 s heavy duty)
Isolation:
between power and control terminals
Regulation Loop:
adjustable PID regulator
Analogue Input Type:
AI1, AI2, AI3 software-configurable voltage 0...10 V DC 30 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA/4...20 mA 250 Ohm 12 bits
Relative Symmetric Network Frequency Tolerance:
0.05
Electromagnetic Compatibility:
electrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge immu
class 3C3 according to IEC 60721-3-3 || class 3S3 according to IEC 60721-3-3
Transmission Frame:
RTU
Number Of Addresses:
1-247
Data Format:
8 bits, configurable odd, even or no parity
Shock Resistance:
15 gn 11 ms IEC 60068-2-27
Accuracy:
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input || +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
Device Application:
Industrial Application
Discrete Output Type:
logic output DQ+ 0-1 kHz <= 30 V DC 100 mA || programmable as pulse output DQ+ 0-30 kHz <= 30 V DC 20 mA || logic output DQ- 0-1 kHz <= 30 V DC 100 mA
With Sft Fct Safe Stop 2 (Ss2):
FALSE
Protection Type:
thermal protection motor || safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-c
Continuous Output Current:
18 A 4 kHz normal duty || 13.5 A 4 kHz heavy duty
Local Signalling:
local diagnostic 3 LED mono/dual colour) || presence of voltage 1 LED red) || embedded communication status 3 LED dual colour) || communication module status 4 LED dual colour)
Maximum Deflection Under Vibratory Load (During Operation):
1.5 mm at 2...13 Hz
Width:
171 mm
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Acceleration And Deceleration Ramps:
linear adjustable separately from 0.01...9999 s || S, U or customized
Base Load Current At Low Overload:
18.0 A
Pollution Degree:
2
Supply:
external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection || internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for d
Connector Type:
2 RJ45 || 1 RJ45
With Safety Function Safely Limited Position (Slp):
FALSE
Minimum Switching Current:
relay output R1, R2, R3 5 mA 24 V DC
Rohs Exemption Information:
Yes
Discrete Output Number:
2
Degree Of Protection:
UL type 1
Noise Level:
56 dB 86/188/EEC
With Safety Function Safely Limited Speed (Sls):
TRUE
With Safety Function Safe Speed Monitor (Ssm):
FALSE
Switching Frequency:
2...16 kHz adjustable || 4...16 kHz with derating factor
Prospective Line Isc:
70 kA
Maximum Acceleration Under Vibrational Stress (During Operation):
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Apparent Power:
15.9 kVA 600 V normal duty) || 11.5 kVA 600 V heavy duty)
Operating Position:
vertical +/- 10 degree
Type Of Polarization:
no impedance
Exchange Mode:
half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP