Schneider Electric ATV930D30N4ZU variable speed drive, Altivar Process ATV900, ATV930, 40hp, 380 to 480V, cabinet Integration, IP20, for US
Schneider Electric
$4,618.56
variable speed drive, Altivar Process ATV900, ATV930, 40hp, 380 to 480V, cabinet Integration, IP20, for US
- China Rohs Regulation:
- X
- With Safety Function Safe Stop 1 (Ss1):
- TRUE
- Discrete Output Number:
- 2
- With Safety Function Safe Position (Sp):
- FALSE
- With Safety Function Safe Brake Management (Sbc/Sbt):
- TRUE
- Connector Type:
- 2 RJ45 || 1 RJ45
- Operating Position:
- vertical +/- 10 degree
- With Safety Function Safe Operating Stop (Sos):
- FALSE
- Base Load Current At High Overload:
- 46.3 A
- Phase:
- 3 phase
- Height:
- 597 mm
- Acceleration And Deceleration Ramps:
- linear adjustable separately from 0.01...9999 s
- Range Of Product:
- Altivar Process ATV900
- With Safety Function Safe Programmable Logic:
- FALSE
- Relative Humidity:
- 5-95 % without condensation IEC 60068-2-3
- Type Of Polarization:
- no impedance
- Country of Origin:
- India
- Asynchronous Motor Control Profile:
- constant torque standard || variable torque standard || optimized torque mode
- Mounting Mode:
- cabinet mount
- Maximum Output Frequency:
- 599 Hz
- Base Load Current At Low Overload:
- 61.5 A
- Continuous Output Current:
- 61.5 A 4 kHz normal duty || 46.3 A 4 kHz heavy duty
- Nominal Switching Frequency:
- 4 kHz
- [Us] Rated Supply Voltage:
- 380...480 V - 15...10 %
- Input Compatibility:
- DI1...DI8 discrete input level 1 PLC IEC 61131-2 || DI7, DI8 pulse input level 1 PLC IEC 65A-68 || STOA, STOB discrete input level 1 PLC IEC 61131-2
- Maximum Output Voltage:
- 480.0 V
- Noise Level:
- 71.5 dB 86/188/EEC
- Quantity Per Set:
- 1
- Transmission Frame:
- RTU
- Overvoltage Category:
- III
- Method Of Access:
- slave Modbus TCP
- Maximum Acceleration Under Shock Impact (During Operation):
- 150 m/s² at 11 ms
- Product Certifications:
- TÜV || CSA || UL
- Analogue Input Number:
- 3
- Operating Altitude:
- <= 3280.84 ft (1000 m) without derating || 1000...4800 m with current derating 1 % per 100 m
- Maximum Thdi:
- <48 % from 80...100 % of load IEC 61000-3-12
- Local Signaling:
- local diagnostic 3 LED mono/dual colour) || embedded communication status 5 LED dual colour) || communication module status 2 LED dual colour) || presence of voltage 1 LED red)
- Ambient Air Transport Temperature:
- -40-70°C
- Communication Port Protocol:
- Modbus serial || EtherNet/IP || Modbus TCP
- Mercury Free:
- Yes
- Environmental Characteristic:
- chemical pollution resistance class 3C3 IEC 60721-3-3 || dust pollution resistance class 3S3 IEC 60721-3-3
- Discrete Input Number:
- 10
- Option Card:
- slot A communication module Profibus DP V1 || slot A communication module PROFINET || slot A communication module DeviceNet || slot A communication module EtherCAT || slot A communication module CANopen daisy chain RJ45 || slot A communication module
- Number Of Addresses:
- 1-247
- Marking:
- CE
- Linearity Error:
- AI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AQ1, AQ2 +/- 0.2 % analog output
- Environmental Disclosure:
- ENVPEP2007012EN
- Electrical Connection:
- control screw terminal 0.5...1.5 mm² AWG 20...AWG 16 || line side screw terminal 25...50 mm² AWG 4...AWG 1 || motor screw terminal 25...50 mm² AWG 4...AWG 1 || DC bus screw terminal 25...50 mm² AWG 4...AWG 1
- With Safety Function Safely Limited Speed (Sls):
- TRUE
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold