Schneider Electric ATV950U07N4U Atv950 Ip55 Ultype12 0,75Kw 400V/480V Va
SKU:
ATV950U07N4U
UPC:
3606481284211
MPN:
Condition:
New
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Emc Filter:
integrated || with EMC plate option
Option Card:
slot A communication module Profibus DP V1 || slot A communication module PROFINET || slot A communication module DeviceNet || slot A communication module EtherCAT || slot A communication module CANopen daisy chain RJ45 || slot A communication module
With Sft Fct Safe Stop 2 (Ss2):
FALSE
Assembly Style:
enclosed
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Acceleration And Deceleration Ramps:
linear adjustable separately from 0.01...9999 s
Discrete Output Type:
logic output DQ+ 0-1 kHz <= 30 V DC 100 mA || programmable as pulse output DQ+ 0-30 kHz <= 30 V DC 20 mA || logic output DQ- 0-1 kHz <= 30 V DC 100 mA
1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6 || 1 gn 13-200 Hz)IEC 60068-2-6
Shock Resistance:
15 gn 11 ms IEC 60068-2-27
With Safety Function Safe Position (Sp):
FALSE
Relative Humidity:
5-95 % without condensation IEC 60068-2-3
Discrete Input Logic:
16 preset speeds
Range Of Product:
Altivar Process ATV900
Analogue Output Type:
software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 500 Ohm 10 bits
Linearity Error:
AI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AQ1, AQ2 +/- 0.2 % analog output
Product Certifications:
ABS || UL || ATEX INERIS || TÃV || DNV-GL || CSA || Bureau Veritas
Maximum Output Voltage:
480.0 V
Maximum Acceleration Under Shock Impact (During Operation):
150 m/s² at 11 ms
Maximum Transient Current:
2.6 A 60 s normal duty) || 2.3 A 60 s heavy duty)
Regulation Loop:
adjustable PID regulator
Phase:
3 phase
Discrete Output Number:
2
Pollution Degree:
2
Accuracy:
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input || +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
[Us] Rated Supply Voltage:
380...480 V - 15...10 %
Height:
678 mm
Number Of Addresses:
1-247
With Safety Function Safe Speed Monitor (Ssm):
FALSE
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Operating Position:
vertical +/- 10 degree
Supply:
external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection || internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for d
Maximum Deflection Under Vibratory Load (During Operation):
1.5 mm at 2...13 Hz
Environmental Class (During Operation):
class 3C3 according to IEC 60721-3-3 || class 3S3 according to IEC 60721-3-3
Variant:
standard version || with braking chopper
Mounting Mode:
wall mount
Line Current:
1.5 A 380 V normal duty) || 0.9 A 380 V heavy duty) || 1.3 A 480 V normal duty) || 0.8 A 480 V heavy duty)
Local Signalling:
local diagnostic 3 LED mono/dual colour) || embedded communication status 5 LED dual colour) || communication module status 2 LED dual colour) || presence of voltage 1 LED red)
Ambient Air Transport Temperature:
-40-70 °C
Product Or Component Type:
variable speed drive
Base Load Current At Low Overload:
2.2 A
With Safety Function Safe Brake Management (Sbc/Sbt):
TRUE
Base Load Current At High Overload:
1.5 A
Number Of Addresses:
1-247 Modbus serial
With Safety Function Safe Operating Stop (Sos):
FALSE
Braking To Standstill:
by DC injection
Noise Level:
52 dB
Sustainable Offer Status:
Green Premium product
Motor Slip Compensation:
automatic whatever the load || adjustable || can be suppressed || not available in permanent magnet motor law
With Safety Function Safe Programmable Logic:
FALSE
Transmission Frame:
RTU
Maximum Switching Current:
relay output R1 resistive, cos phi = 1 3 A 250 V AC || relay output R1 resistive, cos phi = 1 3 A 30 V DC || relay output R1 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1 inductive, cos phi = 0.4 7 ms 2 A 30 V DC || relay output R2, R
Circularity Profile:
ENVEOLI1508009EN
Mercury Free:
Yes
Device Application:
Industrial Application
Maximum Thdi:
<48 % full load IEC 61000-3-12
Marking:
CE
Discrete Input Type:
DI1...DI8 programmable, 24 V DC <= 30 V)3.5 kOhm || DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V) || STOA, STOB safe torque off, 24 V DC <= 30 V)> 2.2 kOhm
Permitted Relative Humidity (During Operation):
class 3K5 according to EN 60721-3
Width:
264 mm
Overvoltage Category:
III
Physical Interface:
Ethernet || 2-wire RS 485
Protection Type:
thermal protection motor || safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-c
Motor Power Kw:
0.75 kW normal duty || 0.37 kW heavy duty
Analogue Output Number:
2
Ambient Air Temperature For Storage:
-40-70 °C
Ambient Air Temperature For Operation:
-15-40 °C without derating) || 40-50 °C with derating factor)
AI1, AI2, AI3 software-configurable voltage 0...10 V DC 30 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA/4...20 mA 250 Ohm 12 bits
half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP
Refresh Time:
relay output R1, R2, R3)5 ms +/- 0.5 ms)
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Maximum Acceleration Under Vibrational Stress (During Operation):
10 m/s² at 13...200 Hz
Type Of Polarization:
no impedance Modbus serial
Network Frequency:
50-60 Hz
Relay Output Number:
3
Noise Level:
52 dB 86/188/EEC
With Safety Function Safe Stop 1 (Ss1):
TRUE
With Safety Function Safely Limited Position (Slp):
FALSE
Minimum Switching Current:
relay output R1, R2, R3 5 mA 24 V DC
Electromagnetic Compatibility:
electrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge im
Sampling Duration:
2 ms +/- 0.5 ms DI1...DI8) - discrete input || 5 ms +/- 1 ms DI7, DI8) - pulse input || 1 ms +/- 1 ms AI1, AI2, AI3) - analog input || 5 ms +/- 1 ms AQ1, AQ2) - analog output
Operating Altitude:
<= 3280.84 ft (1000 m) without derating || 1000...4800 m with current derating 1 % per 100 m