Breaking Capacity:
25 kA 208Y/120 V AC 50/60 Hz UL 489 || 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480/277 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz UL 489 || 10 kA 600Y/347 V AC 50/60 Hz UL 489
Product Certifications:
UL || IEC || CCC || EAC || CSA || NOM
Environmental Disclosure:
ENVPEP1610005EN
Ambient Air Temperature For Storage:
-50-85 °C
Line Rated Current:
60-60 A
Product Name:
PowerPact B
Local Signalling:
presence of auxiliary contacts flag green)
Depth:
89 mm
Pvc Free:
Yes
Mounting Height:
76.2 mm
Sustainable Offer Status:
Green Premium product
[Ue] Rated Operational Voltage:
525 V AC 50/60 Hz UL 489
Control Type:
toggle
Device Application:
distribution
Eu Rohs Directive:
Compliant with Exemptions
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Color:
Gray RAL 7016)
Network Frequency:
50/60 Hz
Utilisation Category:
category A
Breaking Capacity Code:
D
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Poles Description:
2P
Height:
137 mm
Pollution Degree:
3 IEC 60947-1
Wire Stripping Length:
20 mm
Ik Degree Of Protection:
IK07 IEC 62262
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Awg Gauge:
AWG 14...AWG 2/0 aluminium/copper
Quality Labels:
CE
[Ui] Rated Insulation Voltage:
800 V IEC 60947-2
Suitability For Isolation:
yes IEC 60947-2
Ambient Air Temperature For Operation:
-25-70 °C
Rohs Exemption Information:
Yes
Electrical Durability:
10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
Width:
54 mm
Phase Connection:
AC
Mounting Mode:
I-Line
Trip Unit Technology:
thermal-magnetic
Circuit Breaker Application:
HACR rated
Tightening Torque:
3.6-4.4 N.m 2.5-6 mm² (AWG 14...AWG 10) || 5-6.2 N.m 10-70 mm² (AWG 8...AWG 2/0)
Electrical Connection:
I-Line connection, line || lugs, load
Product Or Component Type:
circuit breaker
Standards:
NMX J-266 || EN/IEC 60947-5-1 || NEMA AB1 || GB 14048.2 || UL 489 || CSA C22.2 No 5 || EN/IEC 60947-2
Halogen Content Performance:
Halogen free product
9 Mm Pitches:
6
Circularity Profile:
N/A
Ip Degree Of Protection:
front cover IP40 IEC 60529
Number Of Slots:
1 auxiliary switch OF plug-in) || 1 voltage release MN or MX plug-in)
Mechanical Durability:
20000 cycles IEC 947-1 Annex K ed 5.2
Connection Pitch:
27 mm
Range:
PowerPact
Quantity Per Set:
set of 1
Device Short Name:
BD 060
[Ics] Rated Service Breaking Capacity:
25 kA 220...240 V AC 50/60 Hz IEC 60947-2 || 14 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 18 kA 380...415 V AC 50/60 Hz IEC 60947-2 || 18 kA 440 V AC 50/60 Hz IEC 60947-2
Mercury Free:
Yes
Net Weight:
0.952 kg
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Continuous Current Rating:
0.8
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Brochure:
View
Catalog:
View
Datasheet:
View
  • Schneider Electric BDA24060Y2 Molded Case Circuit Brkr 480Y/277V 60A
  • Schneider Electric BDA24060Y2 Molded Case Circuit Brkr 480Y/277V 60A
  • Schneider Electric BDA24060Y2 Molded Case Circuit Brkr 480Y/277V 60A
$714.00

Description

PowerPacT B-Frame brings thermal-mechanical circuit protection in a compact size and offers a wide range of accessories, auxiliaries, and connection options. This PowerPacT B-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 480Y/277VAC. All PowerPacT B-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT B-Frame circuit breakers come in 1 to 4-pole unit mount construction and in 1 to 3-pole I-Line construction. I-Line circuit breakers come with a shrouded I-Line plug on jaw. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT B, 60A, 2 pole, circuit breaker has a breaking capacity of 18kA at 480Y/277VAC. This circuit breaker has a continuous current rating of 80% with an AC phase connection. PowerPacT B circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose