Schneider Electric BGA24100Y4 Molded Case Circuit Brkr 480Y/277V 100A
Schneider Electric
$1,693.50
$1200 Minimum Order for Non-stock Items or $60 Addl Schneider Handling Fee Applies
PowerPacT B-Frame brings thermal-mechanical circuit protection in a compact size and offers a wide range of accessories, auxiliaries, and connection options. This PowerPacT B-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 35kA at 480Y/277VAC. All PowerPacT B-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT B-Frame circuit breakers come in 1 to 4-pole unit mount construction and in 1 to 3-pole I-Line construction. I-Line circuit breakers come with a shrouded I-Line plug on jaw. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT B, 100A, 2 pole, circuit breaker has a breaking capacity of 35kA at 480Y/277VAC. This circuit breaker has a continuous current rating of 80% with a BC phase connection. PowerPacT B circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Device Application:
- distribution
- Quality Labels:
- CE
- Ambient Air Temperature For Operation:
- -25-70 °C
- Suitability For Isolation:
- yes IEC 60947-2
- Depth:
- 89 mm
- Ambient Air Temperature For Storage:
- -50-85 °C
- Height:
- 137 mm
- Ik Degree Of Protection:
- IK07 IEC 62262
- Mounting Mode:
- I-Line
- Color:
- Gray RAL 7016)
- Local Signalling:
- presence of auxiliary contacts flag green)
- Product Name:
- PowerPact B
- Connection Pitch:
- 27 mm
- Tightening Torque:
- 3.6-4.4 N.m 2.5-6 mm² (AWG 14...AWG 10) || 5-6.2 N.m 10-70 mm² (AWG 8...AWG 2/0)
- Eu Rohs Directive:
- Compliant
- Electrical Connection:
- I-Line connection, line || lugs, load
- Quantity Per Set:
- set of 1
- Phase Connection:
- BC
- Product Certifications:
- UL || IEC || CCC || EAC || CSA || NOM
- [Ue] Rated Operational Voltage:
- 525 V AC 50/60 Hz UL 489
- Line Rated Current:
- 100-100 A
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Mercury Free:
- Yes
- Network Frequency:
- 50/60 Hz
- [Ui] Rated Insulation Voltage:
- 800 V IEC 60947-2
- Net Weight:
- 0.952 kg
- Control Type:
- toggle
- Number Of Slots:
- 1 auxiliary switch OF plug-in) || 1 voltage release MN or MX plug-in)
- Circuit Breaker Application:
- HACR rated
- Sustainable Offer Status:
- Green Premium product
- Poles Description:
- 2P
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Standards:
- NEMA AB1 || NMX J-266 || EN/IEC 60947-2 || GB 14048.2 || CSA C22.2 No 5 || UL 489 || EN/IEC 60947-5-1
- Width:
- 54 mm
- Device Short Name:
- BG 100
- Breaking Capacity Code:
- G
- Halogen Content Performance:
- Halogen free product
- Pvc Free:
- Yes
- Product Or Component Type:
- circuit breaker
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Rohs Exemption Information:
- Yes
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220...240 V AC 50/60 Hz IEC 60947-2 || 18 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 35 kA 380...415 V AC 50/60 Hz IEC 60947-2 || 35 kA 440 V AC 50/60 Hz IEC 60947-2
- Mounting Height:
- 76.2 mm
- Breaking Capacity:
- 65 kA 208Y/120 V AC 50/60 Hz UL 489 || 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480/277 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 18 kA 600Y/347 V AC 50/60 Hz UL 489
- Range:
- PowerPact
- Pollution Degree:
- 3 IEC 60947-1
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Awg Gauge:
- AWG 14...AWG 2/0 aluminium/copper
- Wire Stripping Length:
- 20 mm
- Environmental Disclosure:
- ENVPEP1610005EN
- 9 Mm Pitches:
- 6
- Continuous Current Rating:
- 0.8
- Mechanical Durability:
- 20000 cycles IEC 947-1 Annex K ed 5.2
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Trip Unit Technology:
- thermal-magnetic
- Electrical Durability:
- 10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
- Utilisation Category:
- category A
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View