- Pvc Free:
- Yes
- Mounting Mode:
- I-Line
- Mechanical Durability:
- 20000 cycles IEC 947-1 Annex K ed 5.2
- Product Or Component Type:
- circuit breaker
- Pollution Degree:
- 3 IEC 60947-1
- Trip Unit Technology:
- thermal-magnetic
- Connection Pitch:
- 27 mm
- Ambient Air Temperature For Storage:
- -50-85 °C
- [Ui] Rated Insulation Voltage:
- 800 V IEC 60947-2
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Depth:
- 89 mm
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Control Type:
- toggle
- Suitability For Isolation:
- yes IEC 60947-2
- Net Weight:
- 0.952 kg
- Wire Stripping Length:
- 20 mm
- Network Frequency:
- 50/60 Hz
- Quality Labels:
- CE
- Quantity Per Set:
- set of 1
- Ambient Air Temperature For Operation:
- -25-70 °C
- Awg Gauge:
- AWG 14...AWG 2/0 aluminium/copper
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Line Rated Current:
- 45-45 A
- 9 Mm Pitches:
- 6
- Sustainable Offer Status:
- Green Premium product
- Utilisation Category:
- category A
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Product Certifications:
- UL || IEC || CCC || EAC || CSA || NOM
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220...240 V AC 50/60 Hz IEC 60947-2 || 18 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 35 kA 380...415 V AC 50/60 Hz IEC 60947-2 || 35 kA 440 V AC 50/60 Hz IEC 60947-2
- Width:
- 54 mm
- Local Signalling:
- presence of auxiliary contacts flag green)
- Continuous Current Rating:
- 0.8
- Circuit Breaker Application:
- HACR rated
- Mounting Height:
- 76.2 mm
- Device Short Name:
- BG 045
- Tightening Torque:
- 3.6-4.4 N.m 2.5-6 mm² (AWG 14...AWG 10) || 5-6.2 N.m 10-70 mm² (AWG 8...AWG 2/0)
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Number Of Slots:
- 1 auxiliary switch OF plug-in) || 1 voltage release MN or MX plug-in)
- Ik Degree Of Protection:
- IK07 IEC 62262
- Mercury Free:
- Yes
- Range:
- PowerPact
- Height:
- 137 mm
- Poles Description:
- 2P
- Rohs Exemption Information:
- Yes
- Standards:
- UL 489 || EN/IEC 60947-2 || NMX J-266 || NEMA AB1 || CSA C22.2 No 5 || GB 14048.2 || EN/IEC 60947-5-1
- Color:
- Gray RAL 7016)
- Eu Rohs Directive:
- Compliant
- [Ue] Rated Operational Voltage:
- 525 V AC 50/60 Hz UL 489
- Breaking Capacity:
- 65 kA 208Y/120 V AC 50/60 Hz UL 489 || 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480/277 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 250 V DC UL 489 || 20 kA 600Y/347 V AC 50/60 Hz UL 489
- Halogen Content Performance:
- Halogen free product
- Electrical Connection:
- I-Line connection, line || lugs, load
- Environmental Disclosure:
- ENVPEP1610005EN
- Breaking Capacity Code:
- G
- Electrical Durability:
- 10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
- Product Name:
- PowerPact B
- Device Application:
- distribution
- Phase Connection:
- AB
- QN-QUOTE-REQUEST:
- true