Schneider Electric

Schneider Electric CAD50SD TeSys Deca control relay - 5 NO - <= 690 V - 72 V DC standard coil

(No reviews yet) Write a Review
SKU:
CAD50SD
MPN:
CAD50SD
Condition:
New
Mercury Free:
Yes
Standards:
EN/IEC 60947-5-1 || GB/T 14048.5 || UL 60947-5-1 || CSA C22.2 No 60947-5-1 || JIS C8201-5-1
Environmental Disclosure:
ENVPEP110230EN
Protective Treatment:
TH IEC 60068
Depth:
93 mm
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Ip Degree Of Protection:
IP2X front face VDE 0106
Ambient Air Temperature For Storage:
-60-80°C
Control Circuit Voltage Limits:
0.1...0.25 Uc -40-70°C drop-out DC || 0.7...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
Mechanical Durability:
30 Mcycles
Irms Rated Making Capacity:
140 A AC IEC 60947-5-1 || 250 A DC IEC 60947-5-1
[Icw] Rated Short-Time Withstand Current:
100 A - 1 s || 120 A - 500 ms || 140 A - 100 ms
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Country of Origin:
France
Sustainable Offer Status:
Green Premium product
Eu Rohs Directive:
Compliant with Exemptions
Product Or Component Type:
control relay
Range:
TeSys || TeSys Deca
Warranty:
18 months
[Uc] Control Circuit Voltage:
72 V DC
Weight:
0.58 kg
Net Weight:
0.58 kg
Operating Time:
53...72 ms coil energisation and NO closing || 16...24 ms coil de-energisation and NO opening
Associated Fuse Rating:
10 A gG conforming to IEC 60947-5-1
Control Circuit Type:
DC standard
Pole Contact Composition:
5 NO
Hold-In Power Consumption In W:
5.4-5.4 W 20°C
Circularity Profile:
ENVEOLI1102030EN
Product Name:
TeSys CAD
Insulation Resistance:
> 10 MOhm
Device Short Name:
CAD
Non-Overlap Time:
1.5 ms on energisation between NC and NO contact || 1.5 ms on de-energisation between NC and NO contact
Product Certifications:
CB || CCC || UL || CSA || EAC || CE || UKCA
Time Constant:
28 ms
Utilisation Category:
AC-15 || DC-13 || AC-14
Contactor Application:
control circuit
Ambient Air Temperature For Operation:
-40-60°C || 60-70°C with derating
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C)
Tightening Torque:
1.2 N.m screw clamp terminals Philips No 2 || 1.2 N.m screw clamp terminals flat Ø 6 mm || 1.2 N.m screw clamp terminals pozidriv No 2
Operating Altitude:
0...9842.52 ft (0...3000 m)
Connections - Terminals:
screw clamp terminals 1 1-4 mm²flexible without cable end || screw clamp terminals 2 1-4 mm²flexible without cable end || screw clamp terminals 1 1-4 mm²flexible with cable end || screw clamp terminals 2 1-2.5 mm²flexible with cable end || sc
Inrush Power In W:
5.4-5.4 W 20°C)
Minimum Switching Voltage:
17 V
[Ue] Rated Operational Voltage:
<= 690 V AC 25...400 Hz
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
$112.20

Description

TeSys D control relay, 5 contacts (5NO), 10A/690V, for control of electromagnetic loads AC-15/DC-13. It provides a 72V DC control circuit with no inrush consumption and equipped with a surge suppression device, connection by screw clamp terminals. For high operating rates until 180 cycles/min and ambient temperature -40/+60°C, it procures high reliability and durability. Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium product (RoHS/REACh).
View AllClose