Schneider Electric EGB36045 Miniature Circuit Breaker 600V 45A

(No reviews yet) Write a Review
SKU:
EGB36045
UPC:
785901406693
Condition:
New
Local Signalling:
trip indicator
Width:
2.94 in
Product Or Component Type:
circuit-breaker
Tightening Torque:
3.9-3.9 N.m 2.5-6 mm² (AWG 14...AWG 10) || 5.6-5.6 N.m 10-70 mm² (AWG 8...AWG 2/0)
Holding Current:
630 A
Depth:
4.05 in
Circuit Breaker Application:
HACR rated
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Rohs Exemption Information:
Yes
Warranty:
18 months
Breaking Capacity:
18 kA 600Y/347 V AC
Breaking Capacity Code:
G
Number Of Spaces:
3
Height:
5.66 in
Number Of Spaces Required:
3
Ambient Air Temperature For Operation:
40 °C
Trip Unit Rating:
1800-1800 A
Line Rated Current:
45 A
Range Of Product:
125 A Frame EDB-EGB-EJB
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Product Certifications:
cULus
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Module Type:
E-Frame
Trip Unit Technology:
thermal-magnetic
Net Weight:
4 lb(US)
Protection Type:
overload || short-circuit
Product Destination:
NF panelboard
Mounting Mode:
bolt-on
Mercury Free:
Yes
Number Of Poles:
3
Device Short Name:
EGB
[Ue] Rated Operational Voltage:
600Y/347 V AC
Electrical Connection:
lugs aluminium
Awg Gauge:
AWG 12...AWG 2/0 aluminium || AWG 14...AWG 2/0 copper
Brochure:
View
Catalog:
View
Datasheet:
View
$1,131.00

Description

E-Frame Breaker are Lighting Panelboard Circuit breakers that are proven effective and reliable which provide a wide variety or robust features that are use specifically in Square D NF Panelboards. This range of breaker is ideally designed to offer superior overload and short circuit protection. All E-Frame breakers have a thermal-magnetic trip unit as well as signal indicator that will indicate when a trip has occur. Mounting bolts are used to hold these breakers in place. This E-Frame breaker is 45A, 3 pole, and has an operating voltage of 600Y/347 VAC. It also provides a 65 kA max interrupt rating at 120 VAC. This device has a hold current of 630A which is the maximum current the breaker can be held to ensure it will trip and a trip current of 1800A which is the current value when the breaker is guaranteed to trip. Many accessories are available for this breaker. This breaker was calibrated for 40 degrees C. This product is UL Listed as High Intensity Discharge. HACR rated.
View AllClose