Schneider Electric

Schneider Electric GV4PE25S Motor circuit breaker, TeSys GV4, 3P, 25A, Icu 100kA, thermal magnetic, Everlink terminals

(No reviews yet) Write a Review
SKU:
GV4PE25S
MPN:
GV4PE25S
Condition:
New
Pvc Free:
Yes
Weight:
1.45 kg
Environmental Disclosure:
ENVPEP1704004EN
Poles Description:
3P
Line Rated Current:
25 A
Motor Power Kw:
7.5-7.5 kW 660...690 V AC 50/60 Hz || 5.5-5.5 kW 400...415 V AC 50/60 Hz || 7.5-7.5 kW 500 V AC 50/60 Hz || 9-9 kW 660...690 V AC 50/60 Hz || 11-11 kW 660...690 V AC 50/60 Hz || 7.5-7.5 kW 400...415 V AC 50/60 Hz || 9-9 kW 400...415 V AC 50/60 Hz ||
Breaking Capacity:
120 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 || 70 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 30 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 18 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 100 kA 208Y/120 V AC
Sustainable Offer Status:
Green Premium product
Utilisation Category:
category A IEC 60947-2 || AC-3 IEC 60947-4-1
Product Certifications:
IEC || UL || CSA || CCC || EAC || ATEX || EU-RO MR
Ip Degree Of Protection:
IP40 IEC 60529
Fire Resistance:
960°C IEC 60695-2-11
Range Of Product:
TeSys GV4
Rated Duty:
continuous IEC 60947-4-1
Power Dissipation Per Pole:
4.6 W
Product Name:
TeSys GV4 || TeSys Deca
Operating Altitude:
5000 m
Standards:
CSA C22.2 No 60947-4-1 || UL 60947-4-1 || EN/IEC 60947-4-1 || EN/IEC 60947-2
Climatic Withstand:
IACS E10
Operating Position:
any position
Net Weight:
1.45 kg
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Eu Rohs Directive:
Compliant with Exemptions
Electrical Durability:
40000 cycles AC-3 440 V In/2 || 20000 cycles AC-3 440 V In
Ik Degree Of Protection:
IK07 IEC 62262
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Mechanical Durability:
40000 cycles
Device Application:
motor protection
Circularity Profile:
ENVEOLI1704004EN
Magnetic Tripping Current:
425-425 A
Trip Unit Technology:
electronic || thermal-magnetic
Rohs Exemption Information:
Yes
Warranty:
18 months
[Ui] Rated Insulation Voltage:
800 V AC 50/60 Hz IEC 60947-2
Control Type:
toggle
Range:
TeSys Deca
Mercury Free:
Yes
Ambient Air Temperature For Operation:
-25-70°C
Connections - Terminals:
EverLink BTR screw connectors top) 1 1.5-70 mm² - solid || EverLink BTR screw connectors top) 1 1.5-50 mm² - flexible || EverLink BTR screw connectors bottom) 1 2.5-95 mm² - solid || EverLink BTR screw connectors bottom) 1 2.5-70 mm² - flexible
Mechanical Robustness:
vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 || vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 || shocks 15 gn 11 ms IEC 60068-2-27
Pollution Degree:
3
Tightening Torque:
9 N.m 16-95 mm² || 5 N.m 1.5-10 mm²
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Depth:
116 mm
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Color:
Gray RAL 7016)
$845.00

Description

TeSys GV motor circuit breaker, 3 poles (3P), 25A/690V, for protection of 3-phase motors 5.5-11kW@400V. It provides thermal magnetic protection and additional motor protection functions, breaking capacity Icu 100kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 10-25A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Additional protections have fixed pick-up and include short time delay protection Isd at 13 Ir, phase unbalance and loss protection, ground fault protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).