Schneider Electric

Schneider Electric GV4PEM115B Motor circuit breaker, TeSys GV4, 3P, 115A, Icu 25kA, thermal magnetic multifunction, Everlink terminals

(No reviews yet) Write a Review
SKU:
GV4PEM115B
MPN:
GV4PEM115B
Condition:
New
Pvc Free:
Yes
Warranty:
18 months
Poles Description:
3P
Depth:
116 mm
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-2
Product Certifications:
IEC || UL || CSA || CCC || EAC || ATEX || EU-RO MR
Color:
Gray RAL 7016)
Eu Rohs Directive:
Compliant with Exemptions
Electrical Durability:
10000 cycles AC-3 440 V In/2 || 5000 cycles AC-3 440 V In
Mercury Free:
Yes
Rohs Exemption Information:
Yes
Range:
TeSys Deca
Product Or Component Type:
motor circuit breaker
Circularity Profile:
ENVEOLI1704004EN
Rated Duty:
continuous IEC 60947-4-1
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Connections - Terminals:
EverLink BTR screw connectors top) 1 1.5-70 mm² - solid || EverLink BTR screw connectors top) 1 1.5-50 mm² - flexible || EverLink BTR screw connectors bottom) 1 2.5-95 mm² - solid || EverLink BTR screw connectors bottom) 1 2.5-70 mm² - flexible
Pollution Degree:
3
Halogen Content Performance:
Halogen free plastic parts product
Line Rated Current:
115 A
Ip Degree Of Protection:
IP40 IEC 60529
Ambient Air Temperature For Storage:
-50-85°C
Standards:
CSA C22.2 No 60947-4-1 || UL 60947-4-1 || EN/IEC 60947-4-1 || EN/IEC 60947-2
Height:
155 mm
Breaking Capacity:
50 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 || 25 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 || 20 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 35 kA 208Y/120 V AC 50/60 Hz UL 60947 || 35 kA 240 V AC 50/60 Hz U
Device Application:
motor protection
Climatic Withstand:
IACS E10
Magnetic Tripping Current:
1955-1955 A
Motor Power Kw:
37-37 kW 400...415 V AC 50/60 Hz || 45-45 kW 400...415 V AC 50/60 Hz || 55-55 kW 400...415 V AC 50/60 Hz || 45-45 kW 500 V AC 50/60 Hz || 55-55 kW 500 V AC 50/60 Hz || 75-75 kW 500 V AC 50/60 Hz || 75-75 kW 660...690 V AC 50/60 Hz || 90-90 kW 660...6
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Fire Resistance:
960°C IEC 60695-2-11
Range Of Product:
TeSys GV4
Device Short Name:
GV4PEM
Tightening Torque:
9 N.m 16-95 mm² || 5 N.m 1.5-10 mm²
Weight:
1.45 kg
Product Name:
TeSys GV4 || TeSys Deca
Sustainable Offer Status:
Green Premium product
Utilisation Category:
category A IEC 60947-2 || AC-3 IEC 60947-4-1
Power Dissipation Per Pole:
4.6 W
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Environmental Disclosure:
ENVPEP1704004EN
Mechanical Durability:
40000 cycles
Mechanical Robustness:
vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 || vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 || shocks 15 gn 11 ms IEC 60068-2-27
Suitability For Isolation:
yes IEC 60947-1
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Ambient Air Temperature For Operation:
-25-70°C
Trip Unit Technology:
thermal-magnetic || electronic
[Ith] Conventional Free Air Thermal Current:
115 A IEC 60947-4-1
$845.00

Description

TeSys GV motor circuit breaker, 3 poles (3P), 115A/690V, for protection of 3-phase motors 37-55kW@400V. Multifunction circuit breaker, it provides thermal magnetic protection and advanced motor protection, breaking capacity Icu 25kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 65-115A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Advanced protections are adjustable with a smartphone using wireless NFC and include short time delay protection Isd with a setting range 5-13 Ir, phase unbalance and loss protection, ground fault protection, locked rotor (jam), long start. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). It can be equiped externally with 1 or 2 auxiliary SDx modules in order to have alarming and fault differentiation. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
View AllClose