Schneider Electric HDA260302 Molded Case Circuit Breaker 600V 30A
Schneider Electric
$899.00
PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 14kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 30A, 2 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an AC phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Mounting Height:
- 3 in
- Range:
- PowerPact
- Product Name:
- PowerPact H
- Eu Rohs Directive:
- Compliant with Exemptions
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Ambient Air Temperature For Operation:
- -2-70 °C
- Terminal Identifier:
- AL150HD
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Trip Unit Technology:
- thermal-magnetic
- Suitability For Isolation:
- yes IEC 60947-2
- Quantity Per Set:
- 1
- Wire Stripping Length:
- 16 mm
- Mounting Mode:
- I-Line bracket)
- Circuit Breaker Application:
- HACR rated
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Network Frequency:
- 50/60 Hz
- Protected Poles Description:
- 2t
- Line Rated Current:
- 30-30 A
- Product Certifications:
- UL || CSA || NOM
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Height:
- 163 mm
- Device Application:
- distribution
- Environmental Disclosure:
- ENVPEP2206027EN
- Pollution Degree:
- 3 IEC 60947-1
- Control Type:
- toggle
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Ambient Air Temperature For Storage:
- -50-85 °C
- Communication Interface:
- Modbus || Ethernet
- Net Weight:
- 2.2 kg
- Circularity Profile:
- ENVEOLI2206027EN
- Utilisation Category:
- category A
- Depth:
- 86 mm
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- Phase Connection:
- AC
- Pvc Free:
- Yes
- Product Or Component Type:
- circuit breaker
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Poles Description:
- 2P
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Width:
- 104 mm
- Continuous Current Rating:
- 0.8
- Mercury Free:
- Yes
- Quality Labels:
- CE
- Warranty:
- 18 months
- Mounting Support:
- bracket
- Electrical Connection:
- I-Line connection, line || lugs, load
- Sustainable Offer Status:
- Green Premium product
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Rohs Exemption Information:
- Yes
- Magnetic Hold Current:
- 350 A
- Magnetic Tripping Current:
- 750-750 A
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Breaking Capacity Code:
- D
- Color:
- Black
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View