- Device Application:
- distribution
- Mounting Height:
- 3 in
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Mounting Mode:
- I-Line bracket)
- Color:
- Black
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Terminal Identifier:
- AL150HD
- Sustainable Offer Status:
- Green Premium product
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Depth:
- 86 mm
- Wire Stripping Length:
- 16 mm
- Rohs Exemption Information:
- Yes
- Circularity Profile:
- ENVEOLI2206027EN
- Width:
- 104 mm
- Control Type:
- toggle
- Range:
- PowerPact
- Pvc Free:
- Yes
- Ambient Air Temperature For Operation:
- -2-70 °C
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Quality Labels:
- CE
- Quantity Per Set:
- 1
- Mounting Support:
- bracket
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Warranty:
- 18 months
- Protected Poles Description:
- 2t
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Magnetic Tripping Current:
- 850-850 A
- Environmental Disclosure:
- ENVPEP2206027EN
- Line Rated Current:
- 50-50 A
- Pollution Degree:
- 3 IEC 60947-1
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Ambient Air Temperature For Storage:
- -50-85 °C
- Communication Interface:
- Modbus || Ethernet
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Poles Description:
- 2P
- Product Or Component Type:
- circuit breaker
- Breaking Capacity Code:
- D
- Phase Connection:
- CA
- Network Frequency:
- 50/60 Hz
- Mercury Free:
- Yes
- Product Certifications:
- UL || CSA || NOM
- Circuit Breaker Application:
- HACR rated
- Magnetic Hold Current:
- 400 A
- Electrical Connection:
- I-Line connection, line || lugs, load
- Utilisation Category:
- category A
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Trip Unit Technology:
- thermal-magnetic
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Continuous Current Rating:
- 0.8
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Product Name:
- PowerPact H
- Suitability For Isolation:
- yes IEC 60947-2
- Height:
- 163 mm
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Eu Rohs Directive:
- Compliant with Exemptions
- Net Weight:
- 2.2 kg
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- QN-QUOTE-REQUEST:
- true