Magnetic Tripping Current:
1700-1700 A
Magnetic Hold Current:
900 A
Width:
104 mm
Product Or Component Type:
circuit breaker
Quality Labels:
CE
Breaking Capacity:
25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
Height:
163 mm
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Depth:
86 mm
Network Frequency:
50/60 Hz
Quantity Per Set:
1
Circuit Breaker Application:
HACR rated
Rohs Exemption Information:
Yes
Phase Connection:
AB
Ambient Air Temperature For Operation:
-2-70 °C
Pvc Free:
Yes
Net Weight:
2.2 kg
Poles Description:
2P
Circularity Profile:
ENVEOLI2206027EN
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Trip Unit Technology:
thermal-magnetic
Sustainable Offer Status:
Green Premium product
Environmental Disclosure:
ENVPEP2206027EN
Product Certifications:
UL || CSA || NOM
Mounting Height:
3 in
Mounting Mode:
I-Line bracket)
Product Name:
PowerPact H
Control Type:
toggle
Color:
Black
Communication Interface:
Modbus || Ethernet
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Eu Rohs Directive:
Compliant with Exemptions
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Utilisation Category:
category A
Mounting Support:
bracket
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Wire Stripping Length:
16 mm
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
[Ics] Rated Service Breaking Capacity:
25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Pollution Degree:
3 IEC 60947-1
Protected Poles Description:
2t
Mercury Free:
Yes
Continuous Current Rating:
0.8
Line Rated Current:
110-110 A
Terminal Identifier:
AL150HD
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Device Application:
distribution
Ambient Air Temperature For Storage:
-50-85 °C
Breaking Capacity Code:
D
Range:
PowerPact
Local Signalling:
switched off (OFF) 1 trip indicator green)
Ip Degree Of Protection:
front cover IP40 IEC 60529
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Electrical Connection:
I-Line connection, line || lugs, load
Warranty:
18 months
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Suitability For Isolation:
yes IEC 60947-2
Brochure:
View
Catalog:
View
Datasheet:
View
  • Schneider Electric HDA261101 Molded Case Circuit Breaker 600V 110A
  • Schneider Electric HDA261101 Molded Case Circuit Breaker 600V 110A
$2,195.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 14kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 110A, 2 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an AB phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.