Schneider Electric HDA36050 Molded Case Circuit Breaker 600V 50A
Schneider Electric
$1,124.00
PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 14kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 50A, 3 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Product Or Component Type:
- circuit breaker
- Quality Labels:
- CE
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Eu Rohs Directive:
- Compliant with Exemptions
- Pollution Degree:
- 3 IEC 60947-1
- Environmental Disclosure:
- ENVPEP2206027EN
- Pvc Free:
- Yes
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Width:
- 104 mm
- Network Frequency:
- 50/60 Hz
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Rohs Exemption Information:
- Yes
- Magnetic Hold Current:
- 400 A
- Control Type:
- toggle
- Communication Interface:
- Modbus || Ethernet
- Circularity Profile:
- ENVEOLI2206027EN
- Device Application:
- distribution
- Product Name:
- PowerPact H
- Suitability For Isolation:
- yes IEC 60947-2
- Utilisation Category:
- category A
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Ambient Air Temperature For Operation:
- -2-70 °C
- Warranty:
- 18 months
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Color:
- Black
- Poles Description:
- 3P
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Continuous Current Rating:
- 0.8
- Circuit Breaker Application:
- HACR rated
- Phase Connection:
- ABC
- Mounting Support:
- bracket
- Quantity Per Set:
- 1
- Ambient Air Temperature For Storage:
- -50-85 °C
- Trip Unit Technology:
- thermal-magnetic
- Mounting Height:
- 4.5 in
- Protected Poles Description:
- 3t
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Wire Stripping Length:
- 16 mm
- Depth:
- 86 mm
- Mounting Mode:
- I-Line bracket)
- Terminal Identifier:
- AL150HD
- Product Certifications:
- UL || CSA || NOM
- Range:
- PowerPact
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- Net Weight:
- 2.2 kg
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Mercury Free:
- Yes
- Breaking Capacity Code:
- D
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Line Rated Current:
- 50-50 A
- Sustainable Offer Status:
- Green Premium product
- Electrical Connection:
- I-Line connection, line || lugs, load
- Height:
- 163 mm
- Magnetic Tripping Current:
- 850-850 A
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View