- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Eu Rohs Directive:
- Compliant with Exemptions
- Continuous Current Rating:
- 0.8
- Phase Connection:
- ABC
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Communication Interface:
- Modbus || Ethernet
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- Quantity Per Set:
- 1
- Pollution Degree:
- 3 IEC 60947-1
- Environmental Disclosure:
- ENVPEP2206028EN
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Depth:
- 86 mm
- Ambient Air Temperature For Operation:
- -2-70 °C
- Terminal Identifier:
- AL150HD
- Product Name:
- PowerPact H
- Suitability For Isolation:
- yes IEC 60947-2
- Product Or Component Type:
- circuit breaker
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Device Application:
- distribution
- Net Weight:
- 2.2 kg
- Network Frequency:
- 50/60 Hz
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Rohs Exemption Information:
- Yes
- Protected Poles Description:
- 3t
- Width:
- 104 mm
- Poles Description:
- 3P
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Mounting Support:
- bracket
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- Mounting Mode:
- I-Line bracket)
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Pvc Free:
- Yes
- Electrical Connection:
- I-Line connection, line || lugs, load
- Trip Unit Name:
- MicroLogic 3.2 S
- Product Certifications:
- UL || CSA || NOM
- Color:
- Black
- Utilisation Category:
- category A
- Wire Stripping Length:
- 16 mm
- Mounting Height:
- 4.5 in
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.2 S, LSI
- Height:
- 163 mm
- Ambient Air Temperature For Storage:
- -50-85 °C
- Mercury Free:
- Yes
- Range:
- PowerPact
- Circularity Profile:
- ENVEOLI2206028EN
- Breaking Capacity Code:
- D
- Sustainable Offer Status:
- Green Premium product
- Quality Labels:
- CE
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Control Type:
- toggle
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Line Rated Current:
- 60-60 A
- QN-QUOTE-REQUEST:
- true