Schneider Electric HDA36100U31X Molded Case Circuit Breaker 600V 100A
Schneider Electric
$1,569.00
$1200 Minimum Order for Non-stock Items or $60 Addl Schneider Handling Fee Applies
PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides Micrologic Standard with a 3.2 trip unit and an LI function with a breaking capacity of 14kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 100A, 3 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Phase Connection:
- ABC
- Protected Poles Description:
- 3t
- Poles Description:
- 3P
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Product Certifications:
- UL || CSA || NOM
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Range:
- PowerPact
- Eu Rohs Directive:
- Compliant with Exemptions
- Product Name:
- PowerPact H
- Pollution Degree:
- 3 IEC 60947-1
- Breaking Capacity Code:
- D
- Warranty:
- 18 months
- Mounting Height:
- 4.5 in
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Product Or Component Type:
- circuit breaker
- Trip Unit Name:
- MicroLogic 3.2
- Circularity Profile:
- ENVEOLI2206028EN
- Utilisation Category:
- category A
- Mercury Free:
- Yes
- Circuit Breaker Application:
- HACR rated
- Mounting Mode:
- I-Line bracket)
- Width:
- 104 mm
- Terminal Identifier:
- AL150HD
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Quantity Per Set:
- 1
- Communication Interface:
- Modbus || Ethernet
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Environmental Disclosure:
- ENVPEP2206028EN
- Network Frequency:
- 50/60 Hz
- Ambient Air Temperature For Operation:
- -2-70 °C
- Mounting Support:
- bracket
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- Color:
- Black
- Suitability For Isolation:
- yes IEC 60947-2
- Quality Labels:
- CE
- Device Application:
- distribution
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Ambient Air Temperature For Storage:
- -50-85 °C
- Electrical Connection:
- I-Line connection, line || lugs, load
- Depth:
- 86 mm
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.2, LI
- Rohs Exemption Information:
- Yes
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Control Type:
- toggle
- Continuous Current Rating:
- 0.8
- Wire Stripping Length:
- 16 mm
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Line Rated Current:
- 100-100 A
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Height:
- 163 mm
- Sustainable Offer Status:
- Green Premium product
- Net Weight:
- 2.2 kg
- Pvc Free:
- Yes
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View