Schneider Electric HDF26125 Molded Case Circuit Breaker 600V 125A

(No reviews yet) Write a Review
SKU:
HDF26125
UPC:
785901774679
Condition:
New
Device Application:
distribution
Ip Degree Of Protection:
front cover IP40 IEC 60529
Quality Labels:
CE
Breaking Capacity Code:
D
Eu Rohs Directive:
Compliant with Exemptions
Wire Stripping Length:
16 mm
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Circularity Profile:
ENVEOLI2206027EN
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Mounting Support:
busbar
Breaking Capacity:
25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
Local Signalling:
switched off (OFF) 1 trip indicator green)
Color:
Black
Quantity Per Set:
1
Magnetic Hold Current:
900 A
Width:
104 mm
Warranty:
18 months
Product Or Component Type:
circuit breaker
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Ambient Air Temperature For Storage:
-50-85 °C
Height:
163 mm
Terminal Identifier:
AL150HD
Line Rated Current:
125-125 A
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Pvc Free:
Yes
Sustainable Offer Status:
Green Premium product
Continuous Current Rating:
0.8
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Electrical Connection:
busbar connection, line || busbar connection, load
Protected Poles Description:
2t
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Product Name:
PowerPact H
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Circuit Breaker Application:
HACR rated
Mercury Free:
Yes
Suitability For Isolation:
yes IEC 60947-2
Communication Interface:
Modbus || Ethernet
Utilisation Category:
category A
[Ics] Rated Service Breaking Capacity:
25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Rohs Exemption Information:
Yes
Network Frequency:
50/60 Hz
Pollution Degree:
3 IEC 60947-1
Product Certifications:
UL || CSA || NOM
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Poles Description:
2P
Magnetic Tripping Current:
1700-1700 A
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Ambient Air Temperature For Operation:
-2-70 °C
Environmental Disclosure:
ENVPEP2206027EN
Range:
PowerPact
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Mounting Mode:
unit mount busbar)
Depth:
86 mm
Trip Unit Technology:
thermal-magnetic
Control Type:
toggle
Net Weight:
2.2 kg
$2,072.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 14kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has a busbar connection. This PowerPacT H, 125A, 2 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose