Schneider Electric HDL36150T Molded Case Circuit Breaker 600V 150A
Schneider Electric
$3,900.00
PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 14kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT H, 150A, 3 pole, circuit breaker has a breaking capacity of 14kA at 600VAC. This circuit breaker has a continuous current rating of 80%. This unit allows field-interchangeable trip units. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Product Or Component Type:
- circuit breaker
- Magnetic Hold Current:
- 900 A
- Depth:
- 86 mm
- Line Rated Current:
- 150-150 A
- Protected Poles Description:
- 3t
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Mounting Mode:
- unit mount lug)
- Height:
- 163 mm
- Installed Device:
- trip unit field installable
- Utilisation Category:
- category A
- Breaking Capacity Code:
- D
- Pollution Degree:
- 3 IEC 60947-1
- Continuous Current Rating:
- 0.8
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Color:
- Black
- Circuit Breaker Application:
- HACR rated
- Warranty:
- 18 months
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Product Certifications:
- UL || CSA || NOM
- Mercury Free:
- Yes
- Suitability For Isolation:
- yes IEC 60947-2
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Range:
- PowerPact
- Circularity Profile:
- ENVEOLI2206027EN
- Rohs Exemption Information:
- Yes
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Eu Rohs Directive:
- Compliant with Exemptions
- Ambient Air Temperature For Storage:
- -50-85 °C
- Device Application:
- distribution
- Communication Interface:
- Modbus || Ethernet
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Pvc Free:
- Yes
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Width:
- 104 mm
- Network Frequency:
- 50/60 Hz
- Mounting Support:
- lug
- Trip Unit Technology:
- thermal-magnetic
- Quantity Per Set:
- 1
- Sustainable Offer Status:
- Green Premium product
- Electrical Connection:
- lugs, line || lugs, load
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Poles Description:
- 3P
- Wire Stripping Length:
- 16 mm
- Ambient Air Temperature For Operation:
- -2-70 °C
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Quality Labels:
- CE
- Environmental Disclosure:
- ENVPEP2206027EN
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Magnetic Tripping Current:
- 1700-1700 A
- Net Weight:
- 2.2 kg
- Terminal Identifier:
- AL150HD
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Control Type:
- toggle
- Product Name:
- PowerPact H
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View