Magnetic Tripping Current:
1450-1450 A
Network Frequency:
50/60 Hz
Quality Labels:
CE
Net Weight:
2.2 kg
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Magnetic Hold Current:
800 A
Circuit Breaker Application:
HACR rated
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Suitability For Isolation:
yes IEC 60947-2
Mounting Mode:
I-Line bracket)
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Product Name:
PowerPact H
Wire Stripping Length:
16 mm
Width:
104 mm
Utilisation Category:
category A
Pvc Free:
Yes
Product Certifications:
UL || CSA || NOM
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile:
ENVEOLI1311006EN
Rohs Exemption Information:
Yes
Ip Degree Of Protection:
front cover IP40 IEC 60529
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Line Rated Current:
60-60 A
Mounting Support:
bracket
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Communication Interface:
Modbus || Ethernet
Terminal Identifier:
AL150HD
Ambient Air Temperature For Storage:
-50-85 °C
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Quantity Per Set:
1
Warranty:
18 months
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Electrical Connection:
I-Line connection, line || lugs, load
Breaking Capacity Code:
G
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Poles Description:
2P
Mercury Free:
Yes
Protected Poles Description:
2t
Product Or Component Type:
circuit breaker
Local Signalling:
switched off (OFF) 1 trip indicator green)
Depth:
86 mm
Device Application:
distribution
Breaking Capacity:
65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
Eu Rohs Directive:
Compliant
Color:
Black
Range:
PowerPact
Control Type:
toggle
Mounting Height:
3 in
Environmental Disclosure:
ENVPEP1311006EN
Pollution Degree:
3 IEC 60947-1
Phase Connection:
AC
Height:
163 mm
Trip Unit Technology:
thermal-magnetic
Continuous Current Rating:
0.8
Ambient Air Temperature For Operation:
-2-70 °C
Sustainable Offer Status:
Green Premium product
$1,338.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 60A, 2 pole, circuit breaker has a breaking capacity of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an AC phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.