Schneider Electric HGA260604 Molded Case Circuit Breaker 600V 60A

(No reviews yet) Write a Review
SKU:
HGA260604
UPC:
7.85902E+11
Condition:
New
Magnetic Hold Current:
800 A
Ambient Air Temperature For Storage:
-50-85 °C
Pvc Free:
Yes
Magnetic Tripping Current:
1450-1450 A
Mercury Free:
Yes
Breaking Capacity:
65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
Utilisation Category:
category A
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Product Certifications:
UL || CSA || NOM
Range:
PowerPact
Continuous Current Rating:
0.8
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Trip Unit Technology:
thermal-magnetic
Poles Description:
2P
Circuit Breaker Application:
HACR rated
Sustainable Offer Status:
Green Premium product
Line Rated Current:
60-60 A
Eu Rohs Directive:
Compliant
Control Type:
toggle
Net Weight:
2.2 kg
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Network Frequency:
50/60 Hz
Rohs Exemption Information:
Yes
Mounting Mode:
I-Line bracket)
Local Signalling:
switched off (OFF) 1 trip indicator green)
Protected Poles Description:
2t
Ambient Air Temperature For Operation:
-2-70 °C
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Breaking Capacity Code:
G
Environmental Disclosure:
ENVPEP1311006EN
Warranty:
18 months
Product Name:
PowerPact H
Depth:
86 mm
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Terminal Identifier:
AL150HD
Width:
104 mm
Quality Labels:
CE
Device Application:
distribution
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Communication Interface:
Modbus || Ethernet
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Mounting Support:
bracket
Pollution Degree:
3 IEC 60947-1
Wire Stripping Length:
16 mm
Suitability For Isolation:
yes IEC 60947-2
Phase Connection:
BC
Product Or Component Type:
circuit breaker
Mounting Height:
3 in
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Ip Degree Of Protection:
front cover IP40 IEC 60529
Color:
Black
Height:
163 mm
Circularity Profile:
ENVEOLI1311006EN
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Electrical Connection:
I-Line connection, line || lugs, load
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Quantity Per Set:
1
  • Schneider Electric HGA260604 Molded Case Circuit Breaker 600V 60A
  • Schneider Electric HGA260604 Molded Case Circuit Breaker 600V 60A
$2,007.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 60A, 2 pole, circuit breaker has a breaking capacity of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80% with a BC phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose