Schneider Electric HGA36060YP Molded Case Circuit Breaker 600V 60A

(No reviews yet) Write a Review
SKU:
HGA36060YP
UPC:
785901983149
Condition:
New
Communication Interface:
Modbus || Ethernet
Magnetic Hold Current:
800 A
Breaking Capacity Code:
G
Continuous Current Rating:
0.8
Height:
163 mm
Sustainable Offer Status:
Green Premium product
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Product Certifications:
UL || CSA || NOM
Local Signalling:
switched off (OFF) 1 trip indicator green)
Accessory / Separate Part Type:
padlocking device
Phase Connection:
ABC
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Quality Labels:
CE
Product Or Component Type:
circuit breaker
Ip Degree Of Protection:
front cover IP40 IEC 60529
Pollution Degree:
3 IEC 60947-1
Net Weight:
2.2 kg
Electrical Connection:
I-Line connection, line || lugs, load
Color:
Black
Mounting Height:
4.5 in
Mounting Support:
bracket
Circuit Breaker Application:
HACR rated
Width:
104 mm
Product Name:
PowerPact H
Ambient Air Temperature For Storage:
-50-85 °C
Network Frequency:
50/60 Hz
Suitability For Isolation:
yes IEC 60947-2
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Rohs Exemption Information:
Yes
Protected Poles Description:
3t
Quantity Per Set:
1
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Magnetic Tripping Current:
1450-1450 A
Mercury Free:
Yes
Ambient Air Temperature For Operation:
-2-70 °C
Device Application:
distribution
Pvc Free:
Yes
Trip Unit Technology:
thermal-magnetic
Utilisation Category:
category A
Warranty:
18 months
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Eu Rohs Directive:
Compliant
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Wire Stripping Length:
16 mm
Poles Description:
3P
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Mounting Mode:
I-Line bracket)
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Control Type:
toggle
Circularity Profile:
ENVEOLI1311006EN
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Line Rated Current:
60-60 A
Breaking Capacity:
65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
Range:
PowerPact
Depth:
86 mm
Environmental Disclosure:
ENVPEP1311006EN
Terminal Identifier:
AL150HD
Brochure:
View
Catalog:
View
Datasheet:
View
$3,717.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 60A, 3 pole, circuit breaker has a breaking capacity of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. This unit includes a factory installed padlock handle. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.