Schneider Electric HGP36150 Molded Case Circuit Breaker 600V 150A

(No reviews yet) Write a Review
SKU:
HGP36150
UPC:
785901676942
Condition:
New
Breaking Capacity:
65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
Width:
104 mm
Network Frequency:
50/60 Hz
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Mercury Free:
Yes
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Communication Interface:
Modbus || Ethernet
Ambient Air Temperature For Operation:
-2-70 °C
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Electrical Connection:
terminal nut, line || lugs, load
Pollution Degree:
3 IEC 60947-1
Product Or Component Type:
circuit breaker
Circularity Profile:
ENVEOLI1311006EN
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Depth:
86 mm
Local Signalling:
switched off (OFF) 1 trip indicator green)
Line Rated Current:
150-150 A
Mounting Mode:
unit mount lug)
Pvc Free:
Yes
Product Certifications:
UL || CSA || NOM
Height:
163 mm
Environmental Disclosure:
ENVPEP1311006EN
Magnetic Tripping Current:
1700-1700 A
Utilisation Category:
category A
Ip Degree Of Protection:
front cover IP40 IEC 60529
Poles Description:
3P
Rohs Exemption Information:
Yes
Eu Rohs Directive:
Compliant
Wire Stripping Length:
16 mm
Ambient Air Temperature For Storage:
-50-85 °C
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Color:
Black
Circuit Breaker Application:
HACR rated
Protected Poles Description:
3t
Sustainable Offer Status:
Green Premium product
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Breaking Capacity Code:
G
Range:
PowerPact
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Net Weight:
2.2 kg
Product Name:
PowerPact H
Quantity Per Set:
1
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Control Type:
toggle
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Warranty:
18 months
Terminal Identifier:
AL150HD
Quality Labels:
CE
Suitability For Isolation:
yes IEC 60947-2
Device Application:
distribution
Mounting Support:
lug
Trip Unit Technology:
thermal-magnetic
Magnetic Hold Current:
900 A
Continuous Current Rating:
0.8
Brochure:
View
Catalog:
View
Datasheet:
View
$3,599.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has terminal nuts on the line side and lugs on the load side. This PowerPacT H, 150A, 3 pole, circuit breaker has a breaking capacity of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.