- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Warranty:
- 18 months
- Breaking Capacity Code:
- J
- Net Weight:
- 2.2 kg
- Device Application:
- distribution
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Quantity Per Set:
- 1
- Ambient Air Temperature For Storage:
- -50-85 °C
- Color:
- Black
- Utilisation Category:
- category A
- Mounting Height:
- 4.5 in
- Network Frequency:
- 50/60 Hz
- Mercury Free:
- Yes
- Magnetic Tripping Current:
- 750-750 A
- Magnetic Hold Current:
- 350 A
- Line Rated Current:
- 20-20 A
- Height:
- 163 mm
- Pollution Degree:
- 3 IEC 60947-1
- Circuit Breaker Application:
- HACR rated
- Quality Labels:
- CE
- Poles Description:
- 3P
- Control Type:
- toggle
- Ambient Air Temperature For Operation:
- -2-70 °C
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Suitability For Isolation:
- yes IEC 60947-2
- Communication Interface:
- Modbus || Ethernet
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Product Name:
- PowerPact H
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Phase Connection:
- ABC
- Product Certifications:
- UL || CSA || NOM
- Depth:
- 86 mm
- Sustainable Offer Status:
- Green Premium product
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Protected Poles Description:
- 3t
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Wire Stripping Length:
- 16 mm
- Range:
- PowerPact
- Electrical Connection:
- I-Line connection, line || lugs, load
- Eu Rohs Directive:
- Compliant with Exemptions
- Terminal Identifier:
- AL150HD
- Mounting Support:
- bracket
- Trip Unit Technology:
- thermal-magnetic
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- [Ics] Rated Service Breaking Capacity:
- 100 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 65 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 25 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Mounting Mode:
- I-Line bracket)
- Width:
- 104 mm
- Rohs Exemption Information:
- Yes
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Environmental Disclosure:
- ENVPEP2206027EN
- Continuous Current Rating:
- 0.8
- Pvc Free:
- Yes
- Circularity Profile:
- ENVEOLI2206027EN
- Accessory / Separate Part Type:
- padlocking device
- Product Or Component Type:
- circuit breaker
- QN-QUOTE-REQUEST:
- true