PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 25kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 50A, 3 pole, circuit breaker has a breaking capacity of 25kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Phase Connection:
- ABC
- Breaking Capacity Code:
- J
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Poles Description:
- 3P
- Height:
- 163 mm
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Product Certifications:
- UL || CSA || NOM
- Product Name:
- PowerPact H
- Ambient Air Temperature For Storage:
- -50-85 °C
- Terminal Identifier:
- AL150HD
- Mounting Height:
- 4.5 in
- Line Rated Current:
- 50-50 A
- Depth:
- 86 mm
- Utilisation Category:
- category A
- Pollution Degree:
- 3 IEC 60947-1
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Circularity Profile:
- ENVEOLI2206027EN
- Mounting Mode:
- I-Line bracket)
- Environmental Disclosure:
- ENVPEP2206027EN
- Color:
- Black
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Magnetic Hold Current:
- 400 A
- Quantity Per Set:
- 1
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- [Ics] Rated Service Breaking Capacity:
- 100 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 65 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 25 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Mercury Free:
- Yes
- Device Application:
- distribution
- Control Type:
- toggle
- Wire Stripping Length:
- 16 mm
- Net Weight:
- 2.2 kg
- Magnetic Tripping Current:
- 850-850 A
- Communication Interface:
- Modbus || Ethernet
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Network Frequency:
- 50/60 Hz
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Warranty:
- 18 months
- Trip Unit Technology:
- thermal-magnetic
- Pvc Free:
- Yes
- Continuous Current Rating:
- 0.8
- Mounting Support:
- bracket
- Ambient Air Temperature For Operation:
- -2-70 °C
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Eu Rohs Directive:
- Compliant with Exemptions
- Range:
- PowerPact
- Quality Labels:
- CE
- Product Or Component Type:
- circuit breaker
- Circuit Breaker Application:
- HACR rated
- Suitability For Isolation:
- yes IEC 60947-2
- Width:
- 104 mm
- Rohs Exemption Information:
- Yes
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Protected Poles Description:
- 3t
- Electrical Connection:
- I-Line connection, line || lugs, load
- Sustainable Offer Status:
- Green Premium product
- Brochure:
- View
- Catalog:
- View
- Datasheet: