PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides Micrologic Standard with a 3.2 trip unit and an LI function with a breaking capacity of 25kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 150A, 3 pole, circuit breaker has a breaking capacity of 25kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Quantity Per Set:
- 1
- Control Type:
- toggle
- Trip Unit Name:
- MicroLogic 3.2
- Eu Rohs Directive:
- Compliant with Exemptions
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Wire Stripping Length:
- 16 mm
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Phase Connection:
- ABC
- Suitability For Isolation:
- yes IEC 60947-2
- Mounting Height:
- 4.5 in
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Line Rated Current:
- 150-150 A
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Sustainable Offer Status:
- Green Premium product
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Warranty:
- 18 months
- Mercury Free:
- Yes
- Continuous Current Rating:
- 0.8
- Mounting Mode:
- I-Line bracket)
- Color:
- Black
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Ambient Air Temperature For Storage:
- -50-85 °C
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Height:
- 163 mm
- Circularity Profile:
- ENVEOLI2206028EN
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Terminal Identifier:
- AL150HD
- Breaking Capacity Code:
- J
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Ambient Air Temperature For Operation:
- -2-70 °C
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.2, LI
- Environmental Disclosure:
- ENVPEP2206028EN
- Pvc Free:
- Yes
- Communication Interface:
- Modbus || Ethernet
- Net Weight:
- 2.2 kg
- Width:
- 104 mm
- Electrical Connection:
- I-Line connection, line || lugs, load
- Product Or Component Type:
- circuit breaker
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Quality Labels:
- CE
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Device Application:
- distribution
- Rohs Exemption Information:
- Yes
- Utilisation Category:
- category A
- Protected Poles Description:
- 3t
- Circuit Breaker Application:
- HACR rated
- Mounting Support:
- bracket
- [Ics] Rated Service Breaking Capacity:
- 100 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 65 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 25 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Depth:
- 86 mm
- Network Frequency:
- 50/60 Hz
- Product Certifications:
- UL || CSA || NOM
- Pollution Degree:
- 3 IEC 60947-1
- Poles Description:
- 3P
- Range:
- PowerPact
- Product Name:
- PowerPact H
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View