[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Net Weight:
2.2 kg
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Product Name:
PowerPact H
Mounting Support:
lug
Breaking Capacity Code:
J
Color:
Black
Wire Stripping Length:
16 mm
Magnetic Tripping Current:
750-750 A
Trip Unit Technology:
thermal-magnetic
Product Certifications:
UL || CSA || NOM
Mounting Mode:
unit mount lug)
Environmental Disclosure:
ENVPEP2206027EN
Quantity Per Set:
1
Sustainable Offer Status:
Green Premium product
Rohs Exemption Information:
Yes
Local Signalling:
switched off (OFF) 1 trip indicator green)
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Suitability For Isolation:
yes IEC 60947-2
Range:
PowerPact
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Electrical Connection:
lugs, line || lugs, load
Pollution Degree:
3 IEC 60947-1
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Device Application:
distribution
Communication Interface:
Modbus || Ethernet
[Ics] Rated Service Breaking Capacity:
100 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 65 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 25 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Depth:
86 mm
Magnetic Hold Current:
350 A
Pvc Free:
Yes
Product Or Component Type:
circuit breaker
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Ambient Air Temperature For Storage:
-50-85 °C
Circularity Profile:
ENVEOLI2206027EN
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Ambient Air Temperature For Operation:
-2-70 °C
Continuous Current Rating:
0.8
Line Rated Current:
20-20 A
Height:
163 mm
Ip Degree Of Protection:
front cover IP40 IEC 60529
Utilisation Category:
category A
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
Breaking Capacity:
100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Mercury Free:
Yes
Control Type:
toggle
Warranty:
18 months
Circuit Breaker Application:
HACR rated
Network Frequency:
50/60 Hz
Quality Labels:
CE
Width:
104 mm
Terminal Identifier:
AL150HD
Eu Rohs Directive:
Compliant with Exemptions
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Poles Description:
2P
Protected Poles Description:
2t
Brochure:
View
Catalog:
View
Datasheet:
View
  • Schneider Electric HJL26020 Molded Case Circuit Breaker 600V 20A
  • Schneider Electric HJL26020 Molded Case Circuit Breaker 600V 20A
  • Schneider Electric HJL26020 Molded Case Circuit Breaker 600V 20A
$1,559.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 25kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT H, 20A, 2 pole, circuit breaker has a breaking capacity of 25kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose