Schneider Electric HJL36050C Molded Case Circuit Breaker 600V 50A
Schneider Electric
$2,339.00
PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 25kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT H, 50A, 3 pole, circuit breaker has a breaking capacity of 25kA at 600VAC. This circuit breaker has a continuous current rating of 100%. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Line Rated Current:
- 50-50 A
- Circularity Profile:
- ENVEOLI2206027EN
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Net Weight:
- 2.2 kg
- Width:
- 104 mm
- Terminal Identifier:
- AL150HD
- Electrical Connection:
- lugs, line || lugs, load
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Mounting Support:
- lug
- Quality Labels:
- CE
- Color:
- Black
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Device Application:
- distribution
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Mounting Mode:
- unit mount lug)
- Utilisation Category:
- category A
- Trip Unit Technology:
- thermal-magnetic
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Ambient Air Temperature For Storage:
- -50-85 °C
- Rohs Exemption Information:
- Yes
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Breaking Capacity Code:
- J
- Network Frequency:
- 50/60 Hz
- Continuous Current Rating:
- 1
- Circuit Breaker Application:
- HACR rated
- Eu Rohs Directive:
- Compliant with Exemptions
- Mercury Free:
- Yes
- Sustainable Offer Status:
- Green Premium product
- Warranty:
- 18 months
- Pvc Free:
- Yes
- Wire Stripping Length:
- 16 mm
- Magnetic Tripping Current:
- 850-850 A
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Environmental Disclosure:
- ENVPEP2206027EN
- Depth:
- 86 mm
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Product Name:
- PowerPact H
- Quantity Per Set:
- 1
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Ambient Air Temperature For Operation:
- -2-70 °C
- Communication Interface:
- Modbus || Ethernet
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Range:
- PowerPact
- Height:
- 163 mm
- Poles Description:
- 3P
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Magnetic Hold Current:
- 400 A
- Suitability For Isolation:
- yes IEC 60947-2
- Pollution Degree:
- 3 IEC 60947-1
- Product Certifications:
- UL || CSA || NOM
- Protected Poles Description:
- 3t
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Product Or Component Type:
- circuit breaker
- Control Type:
- toggle
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View