Schneider Electric HJP36150 Molded Case Circuit Breaker 600V 150A
Schneider Electric
$5,174.00
PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 25kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has terminal nuts on the line side and lugs on the load side. This PowerPacT H, 150A, 3 pole, circuit breaker has a breaking capacity of 25kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Quality Labels:
- CE
- Breaking Capacity Code:
- J
- Color:
- Black
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Wire Stripping Length:
- 16 mm
- Circularity Profile:
- ENVEOLI2206027EN
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Warranty:
- 18 months
- Mounting Mode:
- unit mount lug)
- Pollution Degree:
- 3 IEC 60947-1
- Electrical Connection:
- terminal nut, line || lugs, load
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Product Certifications:
- UL || CSA || NOM
- Trip Unit Technology:
- thermal-magnetic
- Network Frequency:
- 50/60 Hz
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Sustainable Offer Status:
- Green Premium product
- Environmental Disclosure:
- ENVPEP2206027EN
- Line Rated Current:
- 150-150 A
- Magnetic Tripping Current:
- 1700-1700 A
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Poles Description:
- 3P
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Protected Poles Description:
- 3t
- Height:
- 163 mm
- Utilisation Category:
- category A
- Product Name:
- PowerPact H
- Suitability For Isolation:
- yes IEC 60947-2
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Mounting Support:
- lug
- Device Application:
- distribution
- Range:
- PowerPact
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Ambient Air Temperature For Storage:
- -50-85 °C
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- Continuous Current Rating:
- 0.8
- Width:
- 104 mm
- Magnetic Hold Current:
- 900 A
- Depth:
- 86 mm
- Communication Interface:
- Modbus || Ethernet
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Ambient Air Temperature For Operation:
- -2-70 °C
- Net Weight:
- 2.2 kg
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Rohs Exemption Information:
- Yes
- Terminal Identifier:
- AL150HD
- Product Or Component Type:
- circuit breaker
- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Pvc Free:
- Yes
- Quantity Per Set:
- 1
- Eu Rohs Directive:
- Compliant with Exemptions
- Mercury Free:
- Yes
- Control Type:
- toggle
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View