- Awg Gauge:
- AWG 14...AWG 3/0 aluminium/copper terminal
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Utilisation Category:
- category A
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Ambient Air Temperature For Storage:
- -50-85 °C
- Suitability For Isolation:
- yes IEC 60947-2
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Network Frequency:
- 50/60 Hz
- Electrical Connection:
- terminal nut, line || lugs, load
- Communication Interface:
- Modbus || Ethernet
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Width:
- 104 mm
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Product Certifications:
- UL || CSA || NOM
- Ambient Air Temperature For Operation:
- -2-70 °C
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Pvc Free:
- Yes
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz IEC 60947-3
- Quality Labels:
- CE
- Eu Rohs Directive:
- Compliant
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Sustainable Offer Status:
- Green Premium product
- Magnetic Tripping Current:
- 1450-1450 A
- Protected Poles Description:
- 3t
- Poles Description:
- 3P
- Terminal Identifier:
- AL150HD
- Mounting Support:
- lug
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Wire Stripping Length:
- 16 mm
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Control Type:
- toggle
- Color:
- Black
- Breaking Capacity Code:
- J
- Trip Unit Name:
- MicroLogic 6.2 A
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Pollution Degree:
- 3 IEC 60947-1
- Range:
- PowerPact
- Depth:
- 86 mm
- Circuit Breaker Application:
- HACR rated
- Height:
- 163 mm
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Product Name:
- PowerPact H
- Tightening Torque:
- 5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
- Net Weight:
- 2.2 kg
- Circularity Profile:
- ENVEOLI1311007EN_V2
- Quantity Per Set:
- 1
- Product Or Component Type:
- circuit breaker
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 6.2 A, LSIG
- Continuous Current Rating:
- 0.8
- Mercury Free:
- Yes
- Magnetic Hold Current:
- 800 A
- Mounting Mode:
- unit mount lug)
- Device Application:
- distribution
- Environmental Disclosure:
- ENVPEP1311007EN
- Line Rated Current:
- 150-150 A
- Rohs Exemption Information:
- Yes
- QN-QUOTE-REQUEST:
- true