Schneider Electric HLA36030 Molded Case Circuit Breaker 600V 30A

(No reviews yet) Write a Review
SKU:
HLA36030
UPC:
785901507307
Condition:
New
Mounting Height:
4.5 in
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Quality Labels:
CE
Net Weight:
2.2 kg
Mercury Free:
Yes
Color:
Black
Environmental Disclosure:
ENVPEP2206027EN
Depth:
86 mm
Pollution Degree:
3 IEC 60947-1
Mounting Support:
bracket
Tightening Torque:
5-5 N.m 2.5-6 mm² (AWG 14...AWG 10) || 14-14 N.m 10-95 mm² (AWG 8...AWG 3/0)
Electrical Connection:
I-Line connection, line || lugs, load
Rohs Exemption Information:
Yes
Ip Degree Of Protection:
front cover IP40 IEC 60529
Trip Unit Technology:
thermal-magnetic
Suitability For Isolation:
yes IEC 60947-2
Product Or Component Type:
circuit breaker
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Product Certifications:
UL || CSA || NOM
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Local Signalling:
switched off (OFF) 1 trip indicator green)
Circularity Profile:
ENVEOLI2206027EN
Line Rated Current:
30-30 A
Control Type:
toggle
[Ics] Rated Service Breaking Capacity:
125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Eu Rohs Directive:
Compliant with Exemptions
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-3
Terminal Identifier:
AL150HD
Ambient Air Temperature For Operation:
-2-70 °C
Wire Stripping Length:
16 mm
Breaking Capacity:
125 kA 240 V AC 50/60 Hz UL 489 || 100 kA 480 V AC 50/60 Hz UL 489 || 50 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 50 kA 500 V DC UL 489
Ambient Air Temperature For Storage:
-50-85 °C
Mounting Mode:
I-Line bracket)
Pvc Free:
Yes
Protected Poles Description:
3t
Height:
163 mm
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Phase Connection:
ABC
Utilisation Category:
category A
Poles Description:
3P
Breaking Capacity Code:
L
Awg Gauge:
AWG 14...AWG 3/0 aluminium/copper terminal
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Device Application:
distribution
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Magnetic Tripping Current:
750-750 A
Range:
PowerPact
Continuous Current Rating:
0.8
Sustainable Offer Status:
Green Premium product
Magnetic Hold Current:
350 A
Product Name:
PowerPact H
Width:
104 mm
Quantity Per Set:
1
Network Frequency:
50/60 Hz
Communication Interface:
Modbus || Ethernet
Warranty:
18 months
Circuit Breaker Application:
HACR rated
  • Schneider Electric HLA36030 Molded Case Circuit Breaker 600V 30A
  • Schneider Electric HLA36030 Molded Case Circuit Breaker 600V 30A
  • Schneider Electric HLA36030 Molded Case Circuit Breaker 600V 30A
$2,993.00

Description

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 50kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT H I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This breaker has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT H, 30A, 3 pole, circuit breaker has a breaking capacity of 50kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.