- Net Weight:
- 2.4 kg
- Magnetic Tripping Current:
- 2000-2000 A
- Terminal Identifier:
- AL250JD
- Product Certifications:
- UL || CSA || NOM
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Height:
- 191 mm
- Magnetic Hold Current:
- 1000 A
- Sustainable Offer Status:
- Green Premium product
- Mercury Free:
- Yes
- Accessory / Separate Part Type:
- copper lug
- Protection Type:
- overload protection || short-circuit protection
- Product Name:
- PowerPact J
- Eu Rohs Directive:
- Compliant with Exemptions
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Circularity Profile:
- ENVEOLI2206031EN
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Warranty:
- 18 months
- Product Or Component Type:
- circuit breaker
- Electrical Connection:
- lugs, line || lugs, load
- Environmental Disclosure:
- ENVPEP2206031EN
- Width:
- 104 mm
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Range:
- PowerPact
- Ip Degree Of Protection:
- front cover IP40
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Ambient Air Temperature For Storage:
- -50-85 °C
- Control Type:
- toggle
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Line Rated Current:
- 200-200 A
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Breaking Capacity Code:
- D
- Device Application:
- distribution
- Pvc Free:
- Yes
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Circuit Breaker Application:
- HACR rated
- Depth:
- 86 mm
- Wire Stripping Length:
- 25 mm
- Network Frequency:
- 50/60 Hz
- Mounting Support:
- lug
- Suitability For Isolation:
- yes IEC 60947-2
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Quality Labels:
- CE
- Rohs Exemption Information:
- Yes
- Continuous Current Rating:
- 1
- Mounting Mode:
- unit mount lug)
- Communication Interface:
- Modbus || Ethernet
- Utilisation Category:
- category A
- Pollution Degree:
- 3 IEC 60947-1
- Poles Description:
- 2P
- Trip Unit Technology:
- thermal-magnetic
- Ambient Air Temperature For Operation:
- -2-70 °C
- QN-QUOTE-REQUEST:
- true