- Net Weight:
- 2.4 kg
- Mercury Free:
- Yes
- Pollution Degree:
- 3 IEC 60947-1
- Range:
- PowerPact
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Sustainable Offer Status:
- Green Premium product
- Depth:
- 86 mm
- Accessory / Separate Part Type:
- shunt trip 110...130 V AC compartment
- Phase Connection:
- ABC
- Height:
- 191 mm
- Electrical Connection:
- lugs, line || lugs, load
- Pvc Free:
- Yes
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Product Name:
- PowerPact J
- Continuous Current Rating:
- 0.8
- Magnetic Tripping Current:
- 2250-2250 A
- Product Or Component Type:
- circuit breaker
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Ip Degree Of Protection:
- front cover IP40
- Protection Type:
- overload protection || short-circuit protection
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Utilisation Category:
- category A
- Communication Interface:
- Modbus || Ethernet
- Device Application:
- distribution
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Wire Stripping Length:
- 25 mm
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Network Frequency:
- 50/60 Hz
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Environmental Disclosure:
- ENVPEP2206031EN
- Control Type:
- toggle
- Ambient Air Temperature For Storage:
- -50-85 °C
- Circularity Profile:
- ENVEOLI2206031EN
- Mounting Mode:
- unit mount lug)
- Line Rated Current:
- 225-225 A
- Product Certifications:
- UL || CSA || NOM
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- Circuit Breaker Application:
- HACR rated
- Trip Unit Technology:
- thermal-magnetic
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Magnetic Hold Current:
- 1125 A
- Mounting Support:
- lug
- Eu Rohs Directive:
- Compliant with Exemptions
- Width:
- 104 mm
- Warranty:
- 18 months
- Terminal Identifier:
- AL250JD
- Ambient Air Temperature For Operation:
- -2-70 °C
- Poles Description:
- 3P
- Quality Labels:
- CE
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Breaking Capacity Code:
- D
- Suitability For Isolation:
- yes IEC 60947-2
- Rohs Exemption Information:
- Yes
- Mounting Height:
- 4.5 in
- QN-QUOTE-REQUEST:
- true