- Range:
- PowerPact
- Suitability For Isolation:
- yes IEC 60947-2
- Magnetic Tripping Current:
- 2500-2500 A
- Breaking Capacity Code:
- D
- Product Name:
- PowerPact J
- Continuous Current Rating:
- 0.8
- Pvc Free:
- Yes
- Environmental Disclosure:
- ENVPEP2206031EN
- Poles Description:
- 3P
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Product Or Component Type:
- circuit breaker
- Control Type:
- toggle
- Device Application:
- distribution
- Utilisation Category:
- category A
- Protection Type:
- overload protection || short-circuit protection
- Eu Rohs Directive:
- Compliant with Exemptions
- Rohs Exemption Information:
- Yes
- Phase Connection:
- ABC
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Trip Unit Technology:
- thermal-magnetic
- Mounting Mode:
- unit mount lug)
- Circularity Profile:
- ENVEOLI2206031EN
- Sustainable Offer Status:
- Green Premium product
- Depth:
- 86 mm
- Pollution Degree:
- 3 IEC 60947-1
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Network Frequency:
- 50/60 Hz
- Net Weight:
- 2.4 kg
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Mercury Free:
- Yes
- Electrical Connection:
- lugs, line || terminal nut, load
- Mounting Support:
- lug
- Magnetic Hold Current:
- 1250 A
- Ambient Air Temperature For Storage:
- -50-85 °C
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- Product Certifications:
- UL || CSA || NOM
- Warranty:
- 18 months
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Terminal Identifier:
- AL250JD
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Communication Interface:
- Modbus || Ethernet
- Wire Stripping Length:
- 25 mm
- Width:
- 104 mm
- Height:
- 191 mm
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Circuit Breaker Application:
- HACR rated
- Ip Degree Of Protection:
- front cover IP40
- Line Rated Current:
- 250-250 A
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Ambient Air Temperature For Operation:
- -2-70 °C
- Mounting Height:
- 4.5 in
- Quality Labels:
- CE
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- QN-QUOTE-REQUEST:
- true