- Product Or Component Type:
- circuit breaker
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Ambient Air Temperature For Operation:
- -2-70 °C
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Depth:
- 86 mm
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Accessory / Separate Part Type:
- auxiliary switch 24 V AC/DC 1 NO + 1 NC cover frame
- Breaking Capacity Code:
- G
- Height:
- 191 mm
- Rohs Exemption Information:
- Yes
- Circularity Profile:
- ENVEOLI2206031EN
- Continuous Current Rating:
- 0.8
- Quality Labels:
- CE
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Product Certifications:
- UL || CSA || NOM
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Product Name:
- PowerPact J
- Protection Type:
- overload protection || short-circuit protection
- Communication Interface:
- Modbus || Ethernet
- Magnetic Hold Current:
- 1125 A
- Poles Description:
- 3P
- Trip Unit Technology:
- thermal-magnetic
- Network Frequency:
- 50/60 Hz
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Ambient Air Temperature For Storage:
- -50-85 °C
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Pvc Free:
- Yes
- Net Weight:
- 2.4 kg
- Suitability For Isolation:
- yes IEC 60947-2
- Line Rated Current:
- 225-225 A
- Mercury Free:
- Yes
- Width:
- 104 mm
- Magnetic Tripping Current:
- 2250-2250 A
- Range:
- PowerPact
- Device Application:
- distribution
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Utilisation Category:
- category A
- Wire Stripping Length:
- 25 mm
- Pollution Degree:
- 3 IEC 60947-1
- Terminal Identifier:
- AL250JD
- Environmental Disclosure:
- ENVPEP2206031EN
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Mounting Mode:
- unit mount busbar)
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Mounting Support:
- busbar
- Circuit Breaker Application:
- HACR rated
- Sustainable Offer Status:
- Green Premium product
- Control Type:
- toggle
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Eu Rohs Directive:
- Compliant with Exemptions
- Ip Degree Of Protection:
- front cover IP40
- Electrical Connection:
- busbar connection, line || busbar connection, load
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Warranty:
- 18 months
- QN-QUOTE-REQUEST:
- true