- Product Or Component Type:
- circuit breaker
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Electrical Connection:
- lugs, line || lugs, load
- Circuit Breaker Application:
- HACR rated
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Device Application:
- distribution
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Breaking Capacity Code:
- G
- Ambient Air Temperature For Storage:
- -50-85 °C
- Control Type:
- toggle
- Net Weight:
- 2.4 kg
- Product Certifications:
- UL || CSA || NOM
- Ambient Air Temperature For Operation:
- -2-70 °C
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Communication Interface:
- Modbus || Ethernet
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Eu Rohs Directive:
- Compliant with Exemptions
- Pollution Degree:
- 3 IEC 60947-1
- Product Name:
- PowerPact J
- Wire Stripping Length:
- 25 mm
- Magnetic Tripping Current:
- 350-600 A
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Range:
- PowerPact
- Line Rated Current:
- 125-125 A
- Mounting Mode:
- unit mount lug)
- Environmental Disclosure:
- ENVPEP2206031EN
- Sustainable Offer Status:
- Green Premium product
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Trip Unit Technology:
- thermal-magnetic
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Protection Type:
- overload protection || short-circuit protection
- Mounting Support:
- lug
- Poles Description:
- 3P
- Terminal Identifier:
- AL250JD
- Warranty:
- 18 months
- Network Frequency:
- 50/60 Hz
- Continuous Current Rating:
- 0.8
- Circularity Profile:
- ENVEOLI2206031EN
- Mercury Free:
- Yes
- Utilisation Category:
- category A
- Ip Degree Of Protection:
- front cover IP40
- Quality Labels:
- CE
- Width:
- 104 mm
- Suitability For Isolation:
- yes IEC 60947-2
- Height:
- 191 mm
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Depth:
- 86 mm
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Rohs Exemption Information:
- Yes
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Pvc Free:
- Yes
- QN-QUOTE-REQUEST:
- true