Schneider Electric JJA36250U31X Molded Case Circuit Breaker 600V 250A
Schneider Electric
$5,970.00
$1200 Minimum Order for Non-stock Items or $60 Addl Schneider Handling Fee Applies
PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides Micrologic Standard with a 3.2 trip unit and an LI function with a breaking capacity of 25kA at 600VAC. All PowerPacT J-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT J I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT J, 250A, 3 pole, circuit breaker has a breaking capacity of 25kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Pvc Free:
- Yes
- Net Weight:
- 2.4 kg
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.2, LI
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Width:
- 104 mm
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Suitability For Isolation:
- yes IEC 60947-2
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Eu Rohs Directive:
- Compliant with Exemptions
- Trip Unit Name:
- MicroLogic 3.2
- Mounting Support:
- bracket
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Product Certifications:
- UL || CSA || NOM
- Mounting Mode:
- I-Line bracket)
- Range:
- PowerPact
- Warranty:
- 18 months
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm 1 LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Electrical Connection:
- I-Line connection, line || lugs, load
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Environmental Disclosure:
- ENVPEP2206032EN
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Continuous Current Rating:
- 0.8
- Protection Type:
- overload protection || short-circuit protection
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Ambient Air Temperature For Operation:
- -2-70 °C
- Ip Degree Of Protection:
- front cover IP40
- Poles Description:
- 3P
- Product Name:
- PowerPact J
- Ambient Air Temperature For Storage:
- -50-85 °C
- Circularity Profile:
- ENVEOLI2206032EN
- Height:
- 191 mm
- Mercury Free:
- Yes
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Rohs Exemption Information:
- Yes
- Mounting Height:
- 4.5 in
- Wire Stripping Length:
- 25 mm
- Circuit Breaker Application:
- HACR rated
- Network Frequency:
- 50/60 Hz
- Quality Labels:
- CE
- Sustainable Offer Status:
- Green Premium product
- Communication Interface:
- Modbus || Ethernet
- Terminal Identifier:
- AL250JD
- Product Or Component Type:
- circuit breaker
- Utilisation Category:
- category A
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Control Type:
- toggle
- Depth:
- 86 mm
- Pollution Degree:
- 3 IEC 60947-1
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Breaking Capacity Code:
- J
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Line Rated Current:
- 250-250 A
- Device Application:
- distribution
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View