- Width:
- 104 mm
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Pvc Free:
- Yes
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Electrical Connection:
- I-Line connection, line || lugs, load
- Communication Interface:
- Modbus
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Mounting Height:
- 4.5 in
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Control Type:
- toggle
- Tightening Torque:
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Depth:
- 86 mm
- Warranty:
- 18 months
- Sustainable Offer Status:
- Green Premium product
- Network Frequency:
- 50/60 Hz
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Quality Labels:
- CE
- Continuous Current Rating:
- 0.8
- Trip Unit Technology:
- thermal-magnetic
- Phase Connection:
- AC
- Wire Stripping Length:
- 25 mm
- Protection Type:
- overload protection || short-circuit protection
- Height:
- 191 mm
- Environmental Disclosure:
- ENVPEP2206031EN
- Product Or Component Type:
- circuit breaker
- Awg Gauge:
- AWG 3/0...350 kcmil aluminium/copper terminals
- Breaking Capacity:
- 125 kA 240 V AC 50/60 Hz UL 489 || 100 kA 480 V AC 50/60 Hz UL 489 || 50 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 50 kA 500 V DC UL 489
- Poles Description:
- 2P
- Suitability For Isolation:
- yes IEC 60947-2
- Circularity Profile:
- ENVEOLI2206031EN
- Ip Degree Of Protection:
- front cover IP40
- Magnetic Hold Current:
- 1000 A
- Magnetic Tripping Current:
- 2000-2000 A
- Mounting Mode:
- I-Line bracket)
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Terminal Identifier:
- AL250JD
- Circuit Breaker Application:
- HACR rated
- Pollution Degree:
- 3
- Line Rated Current:
- 200-200 A
- Mounting Support:
- bracket
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Net Weight:
- 2.4 kg
- Ambient Air Temperature For Operation:
- -2-70 °C
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Product Certifications:
- UL || CSA || NOM
- Mercury Free:
- Yes
- Eu Rohs Directive:
- Compliant with Exemptions
- [Ics] Rated Service Breaking Capacity:
- 125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Utilisation Category:
- category A
- Rohs Exemption Information:
- Yes
- Ambient Air Temperature For Storage:
- -50-85 °C
- Breaking Capacity Code:
- L
- QN-QUOTE-REQUEST:
- true