- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Product Or Component Type:
- circuit breaker
- Mercury Free:
- Yes
- Height:
- 191 mm
- Sustainable Offer Status:
- Green Premium product
- [Ics] Rated Service Breaking Capacity:
- 125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Wire Stripping Length:
- 25 mm
- Breaking Capacity:
- 125 kA 240 V AC 50/60 Hz UL 489 || 100 kA 480 V AC 50/60 Hz UL 489 || 50 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 50 kA 500 V DC UL 489
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Line Rated Current:
- 150-150 A
- Mounting Mode:
- I-Line bracket)
- Product Certifications:
- UL || CSA || NOM
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Pvc Free:
- Yes
- Eu Rohs Directive:
- Compliant with Exemptions
- Continuous Current Rating:
- 0.8
- Awg Gauge:
- AWG 4...AWG 4/0 aluminium/copper terminal
- Control Type:
- toggle
- Suitability For Isolation:
- yes IEC 60947-2
- Mounting Support:
- bracket
- Circuit Breaker Application:
- HACR rated
- Width:
- 104 mm
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Utilisation Category:
- category A
- Ambient Air Temperature For Storage:
- -50-85 °C
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Magnetic Hold Current:
- 750 A
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Quality Labels:
- CE
- Ip Degree Of Protection:
- front cover IP40
- Net Weight:
- 2.4 kg
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Trip Unit Technology:
- thermal-magnetic
- Breaking Capacity Code:
- L
- Environmental Disclosure:
- ENVPEP2206031EN
- Depth:
- 86 mm
- Magnetic Tripping Current:
- 1750-1750 A
- Terminal Identifier:
- AL175JD
- Communication Interface:
- Modbus
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Protection Type:
- overload protection || short-circuit protection
- Ambient Air Temperature For Operation:
- -2-70 °C
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Pollution Degree:
- 3
- Phase Connection:
- ABC
- Poles Description:
- 3P
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Tightening Torque:
- 25-25 N.m 25-95 mm² (AWG 4...AWG 4/0)
- Network Frequency:
- 50/60 Hz
- Rohs Exemption Information:
- Yes
- Electrical Connection:
- I-Line connection, line || lugs, load
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Circularity Profile:
- ENVEOLI2206031EN
- Warranty:
- 18 months
- Mounting Height:
- 4.5 in
- QN-QUOTE-REQUEST:
- true