Schneider Electric JRA36250U31X Molded Case Circuit Breaker 600V 250A

(No reviews yet) Write a Review
SKU:
JRA36250U31X
UPC:
7.85902E+11
Condition:
New
Tightening Torque:
25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
Net Weight:
2.4 kg
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Phase Connection:
ABC
Protection Type:
overload protection || short-circuit protection
Poles Description:
3P
Mounting Height:
4.5 in
Environmental Disclosure:
ENVPEP2206032EN
Quality Labels:
CE
Circularity Profile:
ENVEOLI2206032EN
Suitability For Isolation:
yes IEC 60947-2
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Trip Unit Name:
MicroLogic 3.2
[Ics] Rated Service Breaking Capacity:
150 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 125 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 75 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 690 V AC 50/60 Hz IEC 60947-2
Depth:
86 mm
Control Type:
toggle
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Line Rated Current:
250-250 A
Awg Gauge:
AWG 3/0...350 kcmil aluminium/copper terminals
Trip Unit Technology:
electronic, standard, MicroLogic 3.2, LI
Eu Rohs Directive:
Compliant with Exemptions
Rohs Exemption Information:
Yes
Ambient Air Temperature For Operation:
-2-70 °C
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz IEC 60947-3
Ambient Air Temperature For Storage:
-50-85 °C
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Terminal Identifier:
AL250JD
Continuous Current Rating:
0.8
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Utilisation Category:
category A
Height:
191 mm
Network Frequency:
50/60 Hz
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Product Certifications:
UL || CSA || NOM
Pollution Degree:
3
Product Or Component Type:
circuit breaker
Ip Degree Of Protection:
front cover IP40
Width:
104 mm
Long Time Pick-Up Adjustment Range:
0.25...1 x In
Electrical Connection:
I-Line connection, line || lugs, load
Mounting Mode:
I-Line bracket)
Circuit Breaker Application:
HACR rated
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Breaking Capacity:
200 kA 240 V AC 50/60 Hz UL 489 || 200 kA 480 V AC 50/60 Hz UL 489 || 100 kA 600 V AC 50/60 Hz UL 489
Mercury Free:
Yes
Sustainable Offer Status:
Green Premium product
Wire Stripping Length:
25 mm
Mounting Support:
bracket
Breaking Capacity Code:
R
Pvc Free:
Yes
Communication Interface:
Modbus
Local Signalling:
ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm 1 LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
Brochure:
View
Catalog:
View
Datasheet:
View
  • Schneider Electric JRA36250U31X Molded Case Circuit Breaker 600V 250A
  • Schneider Electric JRA36250U31X Molded Case Circuit Breaker 600V 250A
$10,102.00

Description

PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides Micrologic Standard with a 3.2 trip unit and an LI function with a breaking capacity of 100kA at 600VAC. All PowerPacT J-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. PowerPacT J I-Line circuit breakers are available in I-Line construction for easy installation and removal in I-Line applications. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT J, 250A, 3 pole, circuit breaker has a breaking capacity of 100kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose