- Ip Degree Of Protection:
- front cover IP40
- Ambient Air Temperature For Operation:
- -2-70 °C
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Quality Labels:
- CE
- Sustainable Offer Status:
- Green Premium product
- Wire Stripping Length:
- 25 mm
- Height:
- 191 mm
- Mercury Free:
- Yes
- Product Certifications:
- UL || CSA || NOM
- Network Frequency:
- 50/60 Hz
- Product Or Component Type:
- circuit breaker
- Depth:
- 86 mm
- [Ics] Rated Service Breaking Capacity:
- 150 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 125 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 75 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 690 V AC 50/60 Hz IEC 60947-2
- Net Weight:
- 2.4 kg
- Electrical Connection:
- lugs, line || lugs, load
- Breaking Capacity:
- 200 kA 240 V AC 50/60 Hz UL 489 || 200 kA 480 V AC 50/60 Hz UL 489 || 100 kA 600 V AC 50/60 Hz UL 489
- Circuit Breaker Application:
- HACR rated
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Ambient Air Temperature For Storage:
- -50-85 °C
- Tightening Torque:
- 25-25 N.m 25-95 mm² (AWG 4...AWG 4/0)
- Continuous Current Rating:
- 0.8
- Awg Gauge:
- AWG 4...AWG 4/0 aluminium/copper terminal
- Pvc Free:
- Yes
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Width:
- 104 mm
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Communication Interface:
- Modbus
- Circularity Profile:
- ENVEOLI2206031EN
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Pollution Degree:
- 3
- Breaking Capacity Code:
- R
- Poles Description:
- 3P
- Trip Unit Technology:
- thermal-magnetic
- Magnetic Hold Current:
- 750 A
- Line Rated Current:
- 150-150 A
- Magnetic Tripping Current:
- 1750-1750 A
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Suitability For Isolation:
- yes IEC 60947-2
- Control Type:
- toggle
- Mounting Mode:
- unit mount lug)
- Utilisation Category:
- category A
- Environmental Disclosure:
- ENVPEP2206031EN
- Terminal Identifier:
- AL175JD
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Eu Rohs Directive:
- Compliant with Exemptions
- Protection Type:
- overload protection || short-circuit protection
- Local Signalling:
- switched off (OFF) 1 trip indicator green)
- Mounting Support:
- lug
- Rohs Exemption Information:
- Yes
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- QN-QUOTE-REQUEST:
- true