Schneider Electric

Schneider Electric LC1D09D7 IEC contactor, TeSys Deca, nonreversing, 9A, 5HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 42VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC1D09D7
MPN:
LC1D09D7
Condition:
New
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
[Ie] Rated Operational Current:
9 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 25 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 9 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Heat Dissipation:
2-3 W at 50/60 Hz
Tightening Torque:
power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
Insulation Resistance:
> 10 MOhm for Signaling circuit
Width:
45 mm
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Rohs Exemption Information:
Yes
Irms Rated Making Capacity:
250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Power Dissipation Per Pole:
1.56 W AC-1 || 0.2 W AC-3 || 0.2 W AC-3e
Protective Cover:
with
Device Short Name:
LC1D
Protective Treatment:
THIEC 60068-2-30
Eu Rohs Directive:
Compliant
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 25 A gG at <= 690 V coordination type 1 for power circuit || 20 A gG at <= 690 V coordination type 2 for power circuit
Flame Retardance:
V1 conforming to UL 94
[Uc] Control Circuit Voltage:
42 V AC 50/60 Hz
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Product Certifications:
GL || BV || DNV || LROS (Lloyds register of shipping) || RINA || UL || CCC || CSA || GOST || UKCA || CB
Control Circuit Type:
AC 50/60 Hz
Average Impedance:
2.5 mOhm - Ith 25 A 50 Hz for power circuit
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Product Or Component Type:
contactor
Minimum Switching Voltage:
17 V for Signaling circuit
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Country of Origin:
France
Operating Altitude:
0...9842.52 ft (0...3000 m)
Electrical Durability:
0.6 Mcycles 25 A AC-1 <= 440 V || 2 Mcycles 9 A AC-3 <= 440 V || 2 Mcycles 9 A AC-3e <= 440 V
Operating Time:
12...22 ms closing || 4...19 ms opening
Contactor Application:
resistive load || motor control
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Connections - Terminals:
power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 1 1-4 mm² - cable
Maximum Horse Power Rating:
1 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 2 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 2 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 5 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 7.5 hp at 575/600 V AC 50/60 Hz for 3 phas
Auxiliary Contact Composition:
1 NO + 1 NC
Compatibility Code:
LC1D
Rated Breaking Capacity:
250 A at 440 V for power circuit conforming to IEC 60947
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Pole Contact Composition:
3 NO
Height:
77 mm
Pvc Free:
Yes
Environmental Disclosure:
ENVPEP1501004
Maximum Operating Rate:
3600 cyc/h 60°C
Utilisation Category:
AC-1 || AC-4 || AC-3 || AC-3e
Net Weight:
0.32 kg
Fire Resistance:
850°C IEC 60695-2-1
Weight:
0.32 kg
Coil Technology:
without built-in suppressor module
$112.80

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 9A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200-208VAC, 25HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. When used with a 480VAC up to 35A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 25A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 42 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.15 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.71 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose