Protective Cover:
with
Pole Contact Composition:
3 NO
Protective Treatment:
THIEC 60068-2-30
Pollution Degree:
3
Compatibility Code:
LC1D
Contactor Application:
motor control || resistive load
Minimum Switching Current:
5 mA for Signaling circuit
Height:
158 mm
Hold-In Power Consumption In Va:
2-18 VA 60 Hz cos phi 0.3 (at 20°C) || 2-18 VA 50 Hz cos phi 0.3 (at 20°C)
Environmental Disclosure:
ENVPEP060301EN
Irms Rated Making Capacity:
1260 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Country of Origin:
Czechia
Circularity Profile:
ENVEOLI100405EN
Weight:
2.5 kg
Mounting Support:
rail || plate
Connections - Terminals:
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-2.5 mm² -
Electrical Durability:
0.8 Mcycles 200 A AC-1 <= 440 V || 0.95 Mcycles 115 A AC-3 <= 440 V || 0.95 Mcycles 115 A AC-3e <= 440 V
Utilisation Category:
AC-1 || AC-4 || AC-3 || AC-3e
Operating Time:
6...20 ms opening || 20...50 ms closing
Inrush Power In Va:
280-350 VA 60 Hz cos phi 0.8 (at 20°C) || 280-350 VA 50 Hz cos phi 0.8 (at 20°C)
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Heat Dissipation:
3-8 W at 50/60 Hz
Safety Reliability Level:
B10d = 684932 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 10000000 cycles contactor with mechanical load EN/ISO 13849-1
Mercury Free:
Yes
[Uc] Control Circuit Voltage:
230 V AC 50/60 Hz
Coil Technology:
built-in bidirectional peak limiting diode suppressor
Flame Retardance:
V1 conforming to UL 94
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947
Power Dissipation Per Pole:
24 W AC-1 || 7.9 W AC-3 || 7.9 W AC-3e
Product Certifications:
UL || CSA || CCC || UKCA || CE || EAC || Marine
Product Or Component Type:
contactor
Insulation Resistance:
> 10 MOhm for Signaling circuit
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || IEC 60947-4-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1
Depth:
136 mm
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 6 Gn for 11 ms)
Sustainable Offer Status:
Green Premium product
Range Of Product:
TeSys Deca
Operating Altitude:
0...9842.52 ft (0...3000 m)
[Ie] Rated Operational Current:
200 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 115 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 115 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Minimum Switching Voltage:
17 V for Signaling circuit
Average Impedance:
0.6 mOhm - Ith 200 A 50 Hz for power circuit
Maximum Horse Power Rating:
30 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 40 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 75 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 100 hp at 575/600 V AC 50/60 Hz for 3 phase motors
[Icw] Rated Short-Time Withstand Current:
250 A 40°C - 10 min for power circuit || 550 A 40°C - 1 min for power circuit || 950 A 40°C - 10 s for power circuit || 1100 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
Eu Rohs Directive:
Compliant with Exemptions
$479.00

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 115A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 30HP at 200 to 208VAC, 40HP at 240VAC, 75HP at 480VAC and 100HP at 600VAC three phase. When used with a 480VAC up to 250A circuit breaker, this contactor can have a SCCR up to 100kA. When used with a 600VAC up to 250A circuit breaker, this contactor can have a SCCR up to 50kA. When used with 600VAC Class J or CC fuses up to 250A, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 4.72 inches wide and 5.35 inches deep. It weighs 5.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.