Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
[Ith] Conventional Free Air Thermal Current:
25 A (at 60°C) for power circuit || 10 A (at 60°C) for Signaling circuit
Environmental Disclosure:
ENVPEP1501004
Depth:
86 mm
Protective Treatment:
THIEC 60068-2-30
Rated Breaking Capacity:
250 A at 440 V for power circuit conforming to IEC 60947
Irms Rated Making Capacity:
250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Hold-In Power Consumption In Va:
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
[Ie] Rated Operational Current:
25 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 12 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 12 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Warranty:
18 months
Maximum Horse Power Rating:
0.5 hp at 115 V AC 50/60 Hz for 1 phase motors || 2 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 3 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 3 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 7.5 hp at 460/480 V AC 50/60 Hz for 3 phase
Weight:
0.325 kg
Toxic Heavy Metal Free:
Yes
Signaling Circuit Frequency:
25...400 Hz
[Icw] Rated Short-Time Withstand Current:
105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
Fire Resistance:
850°C IEC 60695-2-1
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
[Uc] Control Circuit Voltage:
24 V AC 50/60 Hz
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
Heat Dissipation:
2-3 W at 50/60 Hz
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Product Certifications:
GL || BV || DNV || LROS (Lloyds register of shipping) || RINA || UL || CCC || CSA || GOST || UKCA || CB
Country of Origin:
Indonesia
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
Mercury Free:
Yes
Ip Degree Of Protection:
IP20 front face IEC 60529
Product Or Component Type:
contactor
Sustainable Offer Status:
Green Premium product
Contactor Application:
resistive load || motor control
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Flame Retardance:
V1 conforming to UL 94
Average Impedance:
2.5 mOhm - Ith 25 A 50 Hz for power circuit
Protective Cover:
with
Pvc Free:
Yes
Connections - Terminals:
control circuit: lugs-ring terminals - external diameter: 8 mm || power circuit: lugs-ring terminals - external diameter: 8 mm
Circularity Profile:
ENVEOLI1501004
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Net Weight:
0.325 kg
Minimum Switching Current:
5 mA for Signaling circuit
Mounting Support:
rail || plate
Inrush Power In Va:
70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
Coil Technology:
without built-in suppressor module
Operating Altitude:
0...9842.52 ft (0...3000 m)
$142.80

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 12A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 3HP at 200 to 208VAC, 3HP at 240VAC, 7.5HP at 480VAC and 10HP at 600VAC three phase. Contactor is also rated for 0.5HP at 115VAC and 2HP at 240VAC single phase. Contactor is supplied with a 24 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.72 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.