Schneider Electric

Schneider Electric LC1D38JL IEC contactor, TeSys Deca, nonreversing, 38A, 20HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, low consumption 12VDC coil

(No reviews yet) Write a Review
SKU:
LC1D38JL
MPN:
LC1D38JL
Condition:
New
[Ie] Rated Operational Current:
50 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 38 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 38 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Maximum Operating Rate:
3600 cyc/h 60°C
Environmental Disclosure:
ENVPEP110230EN
Depth:
101 mm
Fire Resistance:
850°C IEC 60695-2-1
Electrical Durability:
1.4 Mcycles 50 A AC-1 <= 440 V || 1.4 Mcycles 38 A AC-3 <= 440 V || 1.4 Mcycles 38 A AC-3e <= 440 V
Maximum Horse Power Rating:
10 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 10 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 5 hp at 240 V AC 50/60 Hz for 1 phase motors || 20 hp at 480 V AC 50/60 Hz for 3 phase motors || 25 hp at 600 V AC 50/60 Hz for 3 phase motors
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Range Of Product:
TeSys Deca
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Insulation Resistance:
> 10 MOhm for Signaling circuit
[Icw] Rated Short-Time Withstand Current:
60 A 40°C - 10 min for power circuit || 430 A 40°C - 1 s for power circuit || 150 A 40°C - 1 min for power circuit || 310 A 40°C - 10 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Ip Degree Of Protection:
IP20 front face IEC 60529
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Warranty:
18 months
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
Power Dissipation Per Pole:
5 W AC-1 || 3 W AC-3 || 3 W AC-3e
Rohs Exemption Information:
Yes
Control Circuit Type:
DC low consumption
[Uc] Control Circuit Voltage:
12 V DC
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 550 A at 440 V for power circuit conforming to IEC 60947
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Weight:
0.54 kg
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Mechanical Durability:
30 Mcycles
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Protective Treatment:
THIEC 60068-2-30
Minimum Switching Voltage:
17 V for Signaling circuit
Eu Rohs Directive:
Compliant with Exemptions
Utilisation Category:
AC-4 || AC-1 || AC-3 || AC-3e
Flame Retardance:
V1 conforming to UL 94
Minimum Switching Current:
5 mA for Signaling circuit
Device Short Name:
LC1D
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Motor Power Kw:
18.5 kW at 500 V AC 50/60 Hz (AC-3) || 18.5 kW at 660...690 V AC 50/60 Hz (AC-3) || 7.5 kW at 400 V AC 50/60 Hz (AC-4) || 18.5 kW at 380...400 V AC 50/60 Hz (AC-3) || 9 kW at 220...230 V AC 50/60 Hz (AC-3) || 18.5 kW at 415...440 V AC 50/60 Hz (AC-3)
Mounting Support:
rail || plate
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2 || contro
Average Impedance:
2 mOhm - Ith 50 A 50 Hz for power circuit
Pvc Free:
Yes
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 63 A gG at <= 690 V coordination type 2 for power circuit
Overvoltage Category:
III
Contactor Application:
motor control || resistive load
Operating Altitude:
0...9842.52 ft (0...3000 m)
$289.20

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 38A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 25HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 80A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a low consumption 12 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.19 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.