Schneider Electric LC1D50AMD IEC contactor, TeSys Deca, nonreversing, 50A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 220VDC coil, open style
Schneider Electric
$306.00
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 50A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 15HP at 200 to 208VAC, 15HP at 240VAC, 40HP at 480VAC and 40HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 7.5HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 110A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 220 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.87 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- [Ui] Rated Insulation Voltage:
- power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
- Protective Cover:
- with
- [Icw] Rated Short-Time Withstand Current:
- 400 A 40°C - 10 s for power circuit || 810 A 40°C - 1 s for power circuit || 84 A 40°C - 10 min for power circuit || 208 A 40°C - 1 min for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
- Height:
- 122 mm
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Overvoltage Category:
- III
- Fire Resistance:
- 850°C IEC 60695-2-1
- Net Weight:
- 0.93 kg
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Climatic Withstand:
- IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
- Tightening Torque:
- control circuit 1.7 N.m EverLink BTR screw connectors flat Ø 6 mm || control circuit 1.7 N.m EverLink BTR screw connectors Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BT
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Reach Free Of Svhc:
- Yes
- Depth:
- 120 mm
- Motor Power Kw:
- 15 kW at 220...230 V AC 50/60 Hz (AC-3) || 22 kW at 380...400 V AC 50/60 Hz (AC-3) || 30 kW at 500 V AC 50/60 Hz (AC-3) || 33 kW at 660...690 V AC 50/60 Hz (AC-3) || 25 kW at 415 V AC 50/60 Hz (AC-3) || 30 kW at 440 V AC 50/60 Hz (AC-3) || 11 kW at 4
- Range Of Product:
- TeSys Deca
- Mechanical Durability:
- 10 Mcycles
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Pole Contact Composition:
- 3 NO
- Connections - Terminals:
- control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - c
- Rated Breaking Capacity:
- 900 A at 440 V for power circuit conforming to IEC 60947
- Operating Time:
- 50±15 % ms closing || 16...24 ms opening
- Time Constant:
- 34 ms
- Mounting Support:
- plate || rail
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Contactor Application:
- resistive load || motor control
- Power Dissipation Per Pole:
- 3.7 W AC-3 || 9.6 W AC-1 || 3.7 W AC-3e
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Pollution Degree:
- 3
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Width:
- 55 mm
- [Uc] Control Circuit Voltage:
- 220 V DC
- Signaling Circuit Frequency:
- 25...400 Hz
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Control Circuit Voltage Limits:
- 0.1...0.3 Uc -40-70°C drop-out DC || 0.75...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
- Electrical Durability:
- 1.45 Mcycles 50 A AC-3 <= 440 V || 0.5 Mcycles 80 A AC-1 <= 440 V || 1.45 Mcycles 50 A AC-3e <= 440 V
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Control Circuit Type:
- DC standard
- Product Certifications:
- CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
- Standards:
- EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || CSA C22.2 No 14 || UL 60947-4-1 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ || IEC 60335-1:Clause 30.2
- Coil Technology:
- built-in bidirectional peak limiting diode suppressor
- Weight:
- 0.93 kg
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Permissible Ambient Air Temperature Around The Device:
- -40-60°C || 60-70°C with derating
- Hold-In Power Consumption In W:
- 7.4-7.4 W 20°C
- Utilisation Category:
- AC-4 || AC-1 || AC-3 || AC-3e
- Device Short Name:
- LC1D
- Country of Origin:
- France