Schneider Electric

Schneider Electric LC1D65AF7 IEC contactor, TeSys Deca, nonreversing, 65A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 110VAC 50/60Hz coil, open

(No reviews yet) Write a Review
SKU:
LC1D65AF7
MPN:
LC1D65AF7
Condition:
New
Device Short Name:
LC1D
Mechanical Durability:
6 Mcycles
Ip Degree Of Protection:
IP20 front face IEC 60529
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
Mounting Support:
rail || plate
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Fire Resistance:
850°C IEC 60695-2-1
Pvc Free:
Yes
Warranty:
18 months
Country of Origin:
United States
Environmental Disclosure:
ENVPEP1503009EN
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Width:
55 mm
Operating Time:
4...19 ms opening || 12...26 ms closing
Circularity Profile:
ENVEOLI1503009EN
Utilisation Category:
AC-4 || AC-1 || AC-3 || AC-3e
Weight:
0.86 kg
Motor Power Kw:
11 kW at 400 V AC 50/60 Hz (AC-4) || 18.5 kW at 220...230 V AC 50/60 Hz (AC-3) || 30 kW at 380...400 V AC 50/60 Hz (AC-3) || 37 kW at 500 V AC 50/60 Hz (AC-3) || 37 kW at 660...690 V AC 50/60 Hz (AC-3) || 18.5 kW at 220...230 V AC 50/60 Hz (AC-3e) ||
[Uc] Control Circuit Voltage:
110 V AC 50/60 Hz
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
Reach Free Of Svhc:
Yes
Climatic Withstand:
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Power Dissipation Per Pole:
9.6 W AC-1 || 6.3 W AC-3 || 6.3 W AC-3e
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Tightening Torque:
control circuit 1.7 N.m EverLink BTR screw connectors flat Ø 6 mm || control circuit 1.7 N.m EverLink BTR screw connectors Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BT
Control Circuit Type:
AC 50/60 Hz standard
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Rohs Exemption Information:
Yes
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 80 A (at 60°C) for power circuit
Net Weight:
0.86 kg
Overvoltage Category:
III
[Ui] Rated Insulation Voltage:
power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
Signaling Circuit Frequency:
25...400 Hz
Protective Cover:
with
Range Of Product:
TeSys Deca
Flame Retardance:
V1 conforming to UL 94
Pollution Degree:
3
Insulation Resistance:
> 10 MOhm for Signaling circuit
Inrush Power In Va:
140-140 VA 60 Hz cos phi 0.75 (at 20°C) || 160-160 VA 50 Hz cos phi 0.75 (at 20°C)
[Ie] Rated Operational Current:
80 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 65 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 65 A (at <60°C) at <= 440 V AC AC-3e for power circuit
Minimum Switching Voltage:
17 V for Signaling circuit
Product Certifications:
CCC || UL || CB Scheme || CSA || CE || UKCA || Marine || EAC
Poles Description:
3P
Pole Contact Composition:
3 NO
Maximum Operating Rate:
3600 cyc/h 60°C
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Heat Dissipation:
4-5 W at 50/60 Hz
Permissible Ambient Air Temperature Around The Device:
-40-60°C || 60-70°C with derating
Coil Technology:
without built-in suppressor module
$386.40

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 125A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 110 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose